8
Installation RS20/22/30/32/40
Release
 
05
 
12/2015
 Supply voltage for PoE power supply units (optional)
 Connect the protective conductor with the ground screw before you set 
up the other connections. When removing the cables, remove the 
protective conductor last.
 Make sure that the cross-section of the protective conductor cable is 
the same size as or bigger than the cross-section of the voltage supply 
cables.
 Only use connection cables that are permitted for the specified 
temperature range.
 Connect only a supply voltage that corresponds to the type plate of 
your device.
 PoE power supply unit RPS90/48V LV:18 V DC to 60 V DC
 PoE power supply unit RPS90/48V HV:48 V DC to 320 V DC or 90 
V AC to 265 V AC
 Install a suitable input fuse in the following cases:
 The neutral conductor or the negative terminal of the supply voltage 
is ungrounded.
 For the supply voltage, you provide a DC voltage greater than 
125 V DC.
See “General technical data” on page 64.
 With AC power supply, use a cable cross-section of at least 0.75 mm² 
(for North America AWG 18) for the current conductor at the voltage 
input.
 With DC power supply, use a cable cross-section of at least 1.0 mm² 
(for North America AWG 16) for the current conductor at the voltage 
input.