5. Test Run
10
A16381TMF2
Table A. Optional Setting Items for Function Selection
No. Item Optional Function
Individual
Setting
Setting
Condition
Contents Setting
1 b1
Set heating temperature
compensation(*1)
00
01
02
03
04
Tset +4
o
C(default setting)(*2)
Tset+0
o
C(no compensation)
Tset+2
o
C (*3)
Tset+3
o
C
Tset+1
o
C
2 b2
Circulator Function during Heating
Thermo-OFF
00
01
Unavailable
Available
3 b3 Not used ×
00
01
00
01
4 b4 Change of lter cleaning period
00
01
02
03
04
1200h(default setting)(*4)
100h
1200h
2500h
No Indication
5 b5 Lock operation mode on controller ×
00
01
Usual setting
Locked (*5)
6 b6
Lock temperature setting on remote
controller
×
00
01
Standard
Fixed
7 b7 Set operation mode as Cooling Unit ×
00
01
Usual setting
Locked
8 b8 Automatic Cool/Heat operation ×
00
01
Unavailable
Available
9 b9 Lock fan speed setting on controller ×
00
01
Standard
Locked
10 bA Not used - - Not Used(Use as 00 setting conditions)
11 bb Set cooling temperature compensation ×
00
01
02
Tset+0
o
C(no compensation, default setting)
Tset–1
o
C
Tset–2
o
C
12 bC Not used -
00
01
00
01
13 bd Not used -
00
01
00
01
14 bE Not used -
00
01
00
01
15 C1 Not used -
00
01
00
01
16 C2 Not used - - Not Used(Use as 00 setting conditions)
17 C3 Not used -
00
01
00
01
18 C4 Not used -
00
01
00
01
19 C5
Static pressure sel. / Increase Fan Hi
speed
00
01
02
Standard static pressure/ Standard speed
High static pressure/ Hi speed 1(*6)
Low static pressure/ Hi speed 2
20 C6
Increase of fan speed at heating
Thermo-OFF
00
01
Unavailable
Available
21 C7
Cancel 3 min. compressor starting
delay
00
01
Standard
Cancellation
22 C8
Sensor selection for indoor temp.
control
00
01
02
Indoor air suction sensor/ average air suction-THM4
Wired controller sensor/ THM4(remote sensor)
Average return air sensor and (controller sensor or
remote sensor)
23 C9 Not used - - Not Used(Use as 00 setting conditions)
24 CA Not used - - Not Used(Use as 00 setting conditions)
25 Cb Selection of forced stoppage logic
00
01
Normally Open
Normally Closed
26 CC Not used -
00
01
00
01
27 Cd Not used -
00
01
00
01
28 CE Not used -
00
01
00
01