5. Test Run
A16381TMF2
11
No. Item Optional Function
Individual
Setting
Setting
Condition
Contents Setting
29 CF Change of Louver Swing Angle
○
00
01
02
Standard setting (7 steps)
Cold dra (5 steps)
High ceilings (5 steps)
30 d1 Turn ON unit aer power outage
○
00
01
Unavailable
Available
31 d2 Not used - - Not Used(Use as 00 setting conditions)
32 d3
Restore unit operation status(ON/OFF)
aer power outage
○
00
01
Unavailable
Available
33 d4
Prevention of low air outlet
temperature in cooling mode(*7)
○
00
01
Unavailable
Available
34 d5
Prevention of low air outlet
temperature in heating mode
○
00
01
Unavailable
Available
35 d6 Not used -
00
01
00
01
36 d7 Not used -
00
01
02
03
04
05
06
07
00
01
02
03
04
05
06
07
37 E1 Not used -
00
01
02
00
01
02
38 E2 Not used -
00
01
00
01
39 E3 Not used -
00
01
00
01
40 E4 Not used -
00
01
02
00
01
02
41 E5 Not used -
00
01
00
01
42 E6
Indoor fan operation time aer cooling
operation stoppage
○
00
01
02
Unavailable
60 min.
120 min.
43 E7 Not used -
00
01
00
01
44 E8
Indoor Unit fan control during heating
Thermo-OFF (remote sensor)
○
00
01
Fan operation is Low speed (default setting)
Fan stopped (with remote sensor) or Slow speed
(without remote sensor)
45 E9 Not used -
00
01
00
01
46 EA Not used -
00
01
00
01
47 Eb
IU Fan speed during cooling thermo-
o
○
00
01
02
Function deactivated (default setting)
Low
Slow
48 EC
Forced Thermo-ON aer cooling
operation stop
○
00
01
Unavailable
Available
49 Ed Not used -
00
01
00
01
50 EE Automatic Fan Speed Control
○
00
01
Unavailable
Available
51 EF
IU fan speed set to Auto allowing High
2 speed
○
00
01
Unavailable
Available
52 F0 Not used - - Not Used(Use as 00 setting conditions)