5. Test Run
16
A16381TMF2
No. Item Optional Function
Individual
Setting
Setting
Condition
Contents Setting
122 q4
Ambient Temperature Setpoint
Restriction
×
00
01
02
03
04
05
06
07
08
-20.0°C (-4°F)
-17.0°C (2°F)
-13.0°C (8°F)
-10.0°C (14°F)
-7.0°C (20°F)
-3.0°C (26°F)
0.0°C (32°F)
-25.0°C (-13°F)
-22.0°C (-8°F)
123 q5
Ambient Temperature Setpoint
Restriction Compensation
×
00
01
02
03
04
05
06
2.5°C (4°F)
3.0°C (5°F)
3.5°C (6°F)
0.5°C (1°F)
1.0°C (2°F)
1.5°C (3°F)
2.0°C (3°F)
124 q6 Heater Selection ×
00
01
Duct Heater
Baseboard Heater
125 q7 Emergency Heat Control ×
00
01
Available
Unavailable
126 q8 Not used -
00
01
00
01
127 q9 Not used -
00
01
00
01
128 qA Not used -
00
01
00
01
129 qb Operation mode with Setback ×
00
01
02
03
Unavailable
COOL only
HEAT only
COOL & HEAT
130 qC
Temp. dierential for the Setback
operation
×
00
01
02
03
04
2.0°C(3°F)
3.0°C(5°F)
4.0°C(7°F)
5.0°C(9°F)
1.0°C (2°F)
131 qd Minimum stop time of Setback ×
00
01
02
03
04
05
06
07
08
09
10
11
10 min.
20 min.
30 min.
40 min.
50 min.
60 min.
70 min.
80 min.
90 min.
100 min.
110 min.
120 min.
132 qE Setback Mode ×
00
01
02
03
Always
Input
Schedule
Manual
133 qF
Operation state aer Setback
operation ends
×
00
01
02
Stop
Run
State before Setback Operation
134 r1 Dual Setpoint ×
00
01
Unavailable
Available
135 r2
Dierential temp. setting of Cooling-
Heating changeover
×
00
01
02
03
04
05
1.0°C (2°F)(Default)
1.5°C (3°F)
2.0°C (3°F)
2.5°C (4°F)
3.0°C (5°F)
0.5°C (1°F)