Chapter 3 Programming
3 – 90
Error name
[Detected when]
Misalignment /
Illegal instruction /
Privileged instruction
[Always]
Microprocessor has detected an exception
processing in application.
Retain identity
mismatch
[Power on]
Retain data memory is undefined status due
to battery empty.
(*2)
Unresolved external
references
[Always]
Unresolved external references are
detected.
Software watchdog
of IEC task expired
[Always]
Actual cycle time has exceeded watchdog
time.
Set longer watchdog time.
Processor load
watchdog
[Always]
Microprocessor load watchdog of all IEC
task has been exceeded.
Set longer interval time of task.
IEC task
configuration failed
[Always]
IEC task configuration has failed.
Division by zero
[DIV executed]
The divisor of division command is 0 in
IEC program.
Load boot project
failed
[Power on]
Checksum value of application (user
program) in FLASH does not match the
checksum calculated.
I/O configuration
error
[Always]
I/O configuration does not match with
actual I/O modules.
Battery voltage is low or battery is
disconnected.
Option board invalid
ID
[Power on]
Hardware error is detected in option board.
Or MICRO-EHV+ does not support the
target option board.
FLASH writing
failure
[FLASH writing]
Failure has been detected in writing
FLASH memory or the number of writing
times has been exceeded.
Parameters in
FLASH check sum
error
[Power on]
Checksum value of parameters in FLASH
(IP address, etc.) does not match the
checksum calculated.
If error cause is removed, error code remains except for error code 71 (battery error).
71 Error and OK LED blinking automatically disappear if battery is replaced to new one.