Chapter 3 Programming
3 – 89
3.26 Troubleshooting
3.26.1 Error indication
MICRO-EHV+ indicates the error by the lighting pattern (ON / blink / OFF) of OK LED. If two or more errors are
detected at the same time, smaller error code has higher priority to be displayed. If error is detected, read the
description following countermeasures depending on error level.
3.26.2 Error code
Cycle power. If it does not solve, contact your local supplier.
Exception status is cleared only by Reset operation.
Execute Reset cold/warm/origin by HX-CODESYS
User program execution does not stop by warning. If you need to activate alarm or
any action by warning, use CmpHitachi_MV library.
Error name
[Detected when]
Microprocessor
failure
[Power on]
Overflow of internal watchdog timer due to
system program error.
System program error
(FLASH)
[Power on]
Checksum value of system program
(Runtime) in FLASH does not match the
checksum calculated.
System RAM failure
[Power on]
Read/write check for system RAM has
failed.
Misalignment /
Illegal instruction /
Privileged instruction
[Always]
Microprocessor has detected an exception
processing in system program. (*1)
System program error
(system RAM)
[Always]
Checksum value of system RAM does not
match the checksum calculated.
MAC address error
[Power on]
MAC address is missing or wrong value.
Data memory failure
[Power on]
Read/write check for data memory (RAM)
has failed.