Temperature
Caution: The following storage system components are not supported in
high-temperature environments. Do not operate the following components at
temperatures of 40°C or higher:
DB60 dense drive tray
Hitachi Vantara-provided service processor (SVP) server
First-generation FMDs (non-DC2 FMDs)
State Controller
DBS/DBSE,
DBL/DBLE
drive trays Dense intermix drive tray (DB60)
Operating 50°F to 104°F
(10°C to 40°C)
50°F to 104°F
(10°C to 40°C)
50°F to 95°F (10°C to 35°C)
Non-operating 14°F to 122°F
(-10°C to 50°C)
14°F to 122°F
(-10°C to 50°C)
14°F to 122°F (-10°C to 50°C)
Transport,
storage
-22°F to 140°F
(-30°C to 60°C)
-22°F to 140°F
(-30°C to 60°C)
-22°F to 140°F (-30°C to 60°C)
Temperature
change rate
(°C/h)
10°C or less
State Controller FMD tray
Operating 50°F to 104°F
(10°C to 40°C)
DKC-F810I-1R6FN/3R2FN/6R4FN/7R0FP/14RFP
drive is installed: 50°F to 104°F (10°C to 40°C)
Non-operating 14°F to 122°F
(-10°C to 50°C)
14°F to 95°F (-10°C to 35°C)
Transport,
storage
-22°F to 140°F
(-30°C to 60°C)
-22°F to 122°F (-30°C to 50°C)
Temperature
change rate
(°C/h)
10°C or less
Environmental specications
Appendix B: System specications