6.3 Alarm code list for CHILLER
6.3.1 CHILLER alarms code list
CHILLER alarm
Description
H-LINK
7SEG1 7SEG2 Code
 
Failure of Water Inlet Temperature Thermistor 20
 
Failure of Water Outlet Temperature Thermistor
(only for single cycle unit)
21
 
Failure of Ambient Temperature Thermistor (open/short) 24
 
No Feedback Signal from Water Pump 26
 
Activation of Freeze Protection Control (only for single cycle unit) 27
 
Alarm of Water Failure (Differential Pressure Switch
or Flow Switch Option)-Condenser
28
 
Alarm of Water Failure (Differential Pressure Switch
or Flow Switch Option)-Evaporator
29
 
Activation of Thermostat for excessively High Water Temperature
(Only single cycle units)
30
 
Activation of additional protection device 31
 
Phase Abnormally 32
 
Error Communication between Control PCB (PCB
C1
, PCB
C2
)33
 
Error communication between Chiller and Remote Controller (H-LINK) 34
 
Error Communication between Expansion Valve PCB and Control PCB 36
 
Incorrect Operation
40~45,
47,47,54