PMML0175A-rev.1 - 6/2008
HARC-MODBUS - xxxxxxxxxxxxxxxxxx
8
HARC-MODBUS - Installation Manual
5.2 DIP switch setting
Name Function Factory setting Description
SW1 Not available
All in off (no function)
SW2 Reset Reset button. To be used in case of program has been locked
SW3
(TELE)
Not available
Factory purposes. Never change it
SW4 Configuration Setting functions
SW5 Configuration Setting functions
SW6 Configuration Setting functions
SW7 Options 2
SW7-1: 0FF-SLAVE / ON-MASTER. To be used in case of several
HARC-MODBUS in the same H-LINK address
SW7-2: OFF - EVENT CONTROL / ON - CHANGE CONTROL
SW7-3: OFF - Parity disabled / ON - Parity enabled
SW7-4: OFF - Even parity / ON - Odd parity
SW7-5: OFF - 19200 Bps / ON - 9600 Bps
SW7-(6~8): Not used
SW8 Options 1
(Application type)
SW8-1: 0FF-PACKAGED / ON-CHILLER. To be set according units
application
SW8-2~8: Not used
SW9 Not available
All in off (no function)
SW10 HARC MODBUS
address
HARC MODBUS address from 1 to 32 by pins 1 to 5
SW11 H-LINK DSW
2-Pins DSW
SW11-1: H-LINK end resistance
SW11-2: H-LINK fuse protection
D4, D11 H-LINK H-LINK transmission
D7 Power Power supply ON/OFF
D9/D10 Not used - -
D12 MODBUS - Modbus communication in RS485
D13 Operation - Normal software operation