Chapter 3 Function and Performance Specifications
3-13
Circuit diagram (23 points type) Circuit diagram (Analog expansion unit)
3.3.7 Analogue Output Specifications
Module type 23 points type module Analog exp. unit
Output channel WY40 WY u06, WY u07
(u : unit number)
0-10V (10.24V max.) 0-10V (10.24V max.)
0-20mA (20.48mA max.) 0-20mA (20.48mA max.)
Output range
4-20mA (20.38mA max.)
Resolution 12 bits
Accuracy ±1 % of full scale
Current output
Allowable load
Output allowable capacity
Output allowable inductance
10 to 500 Ω
Maximum 2000 pF
Maximum 1 H
Voltage output
Allowable load
Output allowable impedance
Maximum 10 kΩ
Maximum 1 µF
Circuit diagram (23 points type) Circuit diagram (Analog expansion unit)