Chapter 2 Specifications
2 – 15
2.14 LED indication
The operating condition and the status of the external I/O can be checked on the LED display of the front cover.
Figure 2.2 Front cover of MICRO-EHV+
Figure 2.3 LED display (64-point type)
(1) POW LED
POW LED indicates whether power is properly supplied to the basic unit.
(2) OK LED
OK LED indicates the status of self-diagnostics.
(3) RUN LED
RUN LED indicates operating status.
(4) STATUS LED
STATUS LED indicates system initialization or FLASH memory writing.
(5) IN LED
IN LED indicates input status.
(6) OUT LED
OUT LED indicates output status.
Power source is supplied.
Power source is not supplied.
Normal operation (PLC is ready to run)
Exception or warning status. Refer to Section 3.26 Troubleshooting.
Initialization status during power-up or Error status. Refer to Section 3.26 Troubleshooting.
Initialization status during power-up or flash memory is being written
If boot project file is corrupt or no boot project is stored in USB and internal FLASH memory initialization during power-up
does not complete, which causes STATUS LED keeps blinking and OK LED does not light up. In this case, download
a right project to recover.