PC-ARFH1E FUNCTIONALITIES
1.8.2.1 General opons conguraon
Room Thermostats:
Congure the wired or wireless room thermostats:
• Thermostat 1: None, wired or wireless
• Wireless Binding ID for Thermostat 1: (1 or 2)
• Thermostat 2: None, wired or wireless
• Wireless Binding ID for Thermostat 2: (1 or 2)
• Compensaon factors (See Compensaon factors secon below)
• Room Temperature Demand OFF: Oset value between seng temperature and thermostat
temperature to switch the system to Demand OFF; this parameter refers to a posive dierence in
heang operaon and a negave dierence in cooling operaon.
• Check RT Address: validaon procedure of the wireless thermostats conguraon
Holiday Mode:
Congure holiday come back
• Year
• Month
• Day
• Returning me
• Seng temperature
• Start/Stop Holiday Mode
Air Eco Oset for Circuit 1-2:
Congure the oset air temperature
for the ECO mode.
Current air temperature seng is
reduced by the indicated parameter
(from 1 to 10 ºC)
Central operaon:
• Control type selecon: Local, air,
water or full. Only available when
Cascade Mode is disabled.
• Enable or disable Cascade Mode,
when the system is connected to a
CASCADE CONTROLLER.
Maximum Seng T. (Air):
• Circuit 1
• Circuit 2
◆ Compensaon factors for Heang / Cooling
The temperature of the water supplied by the YUTAKI unit to the circuits is determined by means
of OTC (See “Water calculaon mode”).
This control determines water temperature according to the outdoor temperature. The higher the
outdoor temperature, the lower the building demand is, and in consequence the temperature of
the water supplied to the circuits is lower. Conversely, the thermal demand of the building rises
in the case of low outdoor temperature, and therefore the temperature of the supplied water
becomes higher.
The room temperature compensaon control allows to modify the water temperature determined
by OTC control according to the seng room temperature and the actual room temperature.
In the case of heang, if the dierence between room temperature and seng temperature is
large, then water temperature is increased by the YUTAKI unit in order to achieve the desired
room temperature in a faster way, thus compensang the thermal dierence between seng
temperature and actual temperature.