21
PMEN0602 rev.0 - 05/2023
1
CONTROLLERCONFIGURATION
PC-ARFH1E FUNCTIONALITIES
1.6.2 Advanced Conguraon
Select the advance conguraon for a complete conguraon.
Press OK buon.
Select the controller type:
Unit: the device controls the unit.
Room: the device acts as a room thermostat of a zone.
Unit + Room: the device controls the unit and acts as a room thermostat.
Select controlled circuits by this device: Room C1, Room C2, Room C1+C2
Select the favourite acon: Eco/Confort, Timer, Night shi.
Select Enabled or Disabled for European summer me.
Select Next and press OK buon .
Congure circuit 1 and circuit 2 OTC: Disabled, Points, Gradient, Fix.
Enable or disable DHW and Swimming Pool.
Select the heang source: HP only, HP + EH, HP + Boiler.
Congure electrical heater use: Starng or Backup.
Congure Boiler type: Parallel or Serial.