PC-ARFH1E FUNCTIONALITIES
   Emergency Operaon
Space Heang:
Enable or disable emergency
operaon for space heang.
Only available in case “Heang
source” on “1.8.2.7 Complementary
Heang conguraon” contains
“Electrical heater or boiler” opon
DHW:
Enable or disable emergency
operaon for DHW. Only available
when electrical heater for DHW is
enabled (by DSW).
Mode:
Selecon of the emergency operaon
mode:
Manual: Emergency operaon is acve
when is manually enabled (by DSW4
pin 4 ON). The emergency mode uses
the heater (space heang or DHW) to
provide the required heang.
Automac: Emergency mode operates
when there is an event of outdoor
unit failure and Demand ON of space
heang (enabled) or DHW (enabled).
1.8.2.10 Inputs, Outputs and Sensors conguraon
Outputs:
There are 8 available outputs
to set. There are condions
of seng depending on the
installaon.
Auxiliary sensors:
There are 7 available auxiliary
sensors to set.
Inputs:
The system allows to set 7
inputs depending on the
operaons and preferences
of the installaon
   List of available inputs:
Disabled
Demand ON/OFF (by default in input 1): Consider both Circuit 1 and Circuit 2 in Demand ON
when the signal is ON.
Demand ON/OFF C1: Consider Circuit 1 in Demand ON when the signal is ON.
Demand ON/OFF C2: Consider Circuit 2 in Demand ON when the signal is ON.
Power Meter 2: To count any pulse received from the power meter 2 and sent to central control
energy consumpon calculaon.
ECO C1 + C2: Switch both Circuit 1 and Circuit 2 to ECO mode when input is closed.
ECO C1 (by default in input 2, if there is circuit 1 in the installaon): Switch Circuit 1 to ECO
mode when input is closed.
ECO C2: Switch Circuit 2 to ECO mode when input is closed.
Forced O: Forbid DHW, space heang and space cooling.
Smart Act / SG1 (Fixed in input 5 if smart acon is enabled): To acve Smart Funcon.