PC-ARFH1E FUNCTIONALITIES
Maximum me:
Maximum me that DHW
operaon can work using
heat pump mode. When the
heat pump is stopped by this
funcon, DHW is sll heated by
DHW heater when it is enabled,
unl other condions request
stoppage.
• Range: OFF, 5 ~250 min
• Only in High Speed control and
Standard mode.
Cycle me:
Denes the minimum me between
2 heat pump cycles of domesc hot
water.
DHW will be able to operate
again aer wait in Thermo o the
specied cycle me.
• Range: 0 ~24 hour
• Only available in Standard mode.
3 / 4
4 / 4
DHW Heater: Only available when DHW
heater is acvated (DSW4 pin 3 ON).
• Waing me: Enable or disable waing
me for DHW heater.
• Electrical Heater waing me: Waing
me for the beginning of electrical
heater operaon since compressor start-
up.
• Only available in High Speed control.
An Legionella:
In order to help prevent against Legionella
in the DHW system, the DHW set point
can be raised to a higher than normal
temperature.
The Legionella protecon only makes
sense if there is a DHW electric heater to
raise the DHW temperature to this high
temperature.
See the possible congurable parameters
below.
Space priority status:
If space priority funcon is enabled, Heat
Pump operaon by DHW mode stops (and
connue with DHW heater, if necessary).
This funcon is only performed if space
heang or space cooling can be done. If it
is not possible, operaon will connue in
DHW normally.
• Only available in Standard mode.
Space priority temperature:
Threshold value of outdoor ambient
temperature for the acvaon of the
space priority funcon.
• Range: -20~0 ºC
• Only available in Standard mode.
◆ An Legionella funcon
Status of an legionella operaon (enabled/disabled)
Specied day for an legionella operaon
Specied me of the day for an legionella operaon
Seng for domesc hot water temperature in an legionella operaon.
Duraon of shock treatment. Between 10 to 60 minutes.