51
PMEN0602 rev.0 - 05/2023
1
MENU
PC-ARFH1E FUNCTIONALITIES
   Electrical heater
Operaon:
Starng: Space Heang electric Heater is switched
ON in case of low water temperature and low
ambient temperature to provide extra capacity to HP.
Backup: Space Heang Electric Heater is switched ON
in case of low ambient temperature (below Bivalent
point) in order to provide extra capacity to HP at
coldest days of winter.
Bivalent point:
Electric heater is enabled to operate in case ambient
temperature goes below this value. Only in case of
Backup opon.
Supply seng oset:
Seng oset for electric Heater. Higher values imply
earlier stoppage of electric heater and vice versa.
Only in case of Backup opon.
Inter stage me:
Time of Electric Heater phase overlapping when there
is switch ON/OFF transion from/to phase 1 to/from
phase 2. Only in case of Backup opon.
Waing me:
Delay me to start Electric
Heater in case all condions
allow Electric Heater to start
aer HP has been started. Only
in case of Backup opon.
Proporonal band:
Control to determine how fast
seng temperature is going
to be reached. Higher values
imply fast achievement of water
seng point and therefore higher
ulizaon of heater.
Reset factor:
Used to guarantee seng
temperature achievement
without surpassing its value.
Higher values imply less ulizaon
of heater.
   Solar combinaon - Total control
DHW maximum me:
Maximum me YUTAKI allows to heat tank
by means Solar. At the end of this me Solar
pump is stopped regardless temperature
condions at Solar Panel.
DHW minimum me:
Minimum Time solar operaon cannot be
performed once it has been stopped due
to DHW Maximum Time or due to low
temperature at solar panel.
DHWT maximum storage temperature:
Maximum DHW temperature that allows
Solar operaon.
Panel minimum temperature:
Minimum temperature of the solar Panel to
allow Solar operaon
Panel overheat temperature:
Maximum panel operaon temperature at
which Solar Pump is set to o in case Panel
sensor reads a temperature above this value
in order to protect system.
In case that the solar pump is stopped due
to panel overheat temperature, the YUTAKI
unit sets solar overheat output to high state
provided that this funcon has been setup
as described in “1.8.2.10 Inputs, Outputs and
Sensors conguraon”
Panel anfreeze temperature:
Minimum Solar panel
temperature at which Solar
Pump is switched ON in order
to protect system against frost
formaon at pipes due to low
ambient temperature.
ΔT connecon:
Allows to specify a dierence
temperature between tank and
Panel temperature to allow solar
operaon. Solar operaon is
allowed in case Panel temperature
is “ΔT connecon” ºC above tank
temperature.
ΔT disconnecon:
Allows to specify a dierence
temperature between tank and
Panel temperature to stop solar
operaon. Solar operaon is not
allowed in case Panel temperature
is “ΔT connecon”ºC below tank
temperature