PC-ARFH1E FUNCTIONALITIES
◆ Electrical heater
Operaon:
• Starng: Space Heang electric Heater is switched
ON in case of low water temperature and low
ambient temperature to provide extra capacity to HP.
• Backup: Space Heang Electric Heater is switched ON
in case of low ambient temperature (below Bivalent
point) in order to provide extra capacity to HP at
coldest days of winter.
Bivalent point:
• Electric heater is enabled to operate in case ambient
temperature goes below this value. Only in case of
Backup opon.
Supply seng oset:
• Seng oset for electric Heater. Higher values imply
earlier stoppage of electric heater and vice versa.
Only in case of Backup opon.
Inter stage me:
• Time of Electric Heater phase overlapping when there
is switch ON/OFF transion from/to phase 1 to/from
phase 2. Only in case of Backup opon.
Waing me:
• Delay me to start Electric
Heater in case all condions
allow Electric Heater to start
aer HP has been started. Only
in case of Backup opon.
Proporonal band:
• Control to determine how fast
seng temperature is going
to be reached. Higher values
imply fast achievement of water
seng point and therefore higher
ulizaon of heater.
Reset factor:
• Used to guarantee seng
temperature achievement
without surpassing its value.
Higher values imply less ulizaon
of heater.
◆ Solar combinaon - Total control
DHW maximum me:
• Maximum me YUTAKI allows to heat tank
by means Solar. At the end of this me Solar
pump is stopped regardless temperature
condions at Solar Panel.
DHW minimum me:
• Minimum Time solar operaon cannot be
performed once it has been stopped due
to DHW Maximum Time or due to low
temperature at solar panel.
DHWT maximum storage temperature:
• Maximum DHW temperature that allows
Solar operaon.
Panel minimum temperature:
• Minimum temperature of the solar Panel to
allow Solar operaon
Panel overheat temperature:
• Maximum panel operaon temperature at
which Solar Pump is set to o in case Panel
sensor reads a temperature above this value
in order to protect system.
• In case that the solar pump is stopped due
to panel overheat temperature, the YUTAKI
unit sets solar overheat output to high state
provided that this funcon has been setup
as described in “1.8.2.10 Inputs, Outputs and
Sensors conguraon”
Panel anfreeze temperature:
• Minimum Solar panel
temperature at which Solar
Pump is switched ON in order
to protect system against frost
formaon at pipes due to low
ambient temperature.
ΔT connecon:
• Allows to specify a dierence
temperature between tank and
Panel temperature to allow solar
operaon. Solar operaon is
allowed in case Panel temperature
is “ΔT connecon” ºC above tank
temperature.
ΔT disconnecon:
• Allows to specify a dierence
temperature between tank and
Panel temperature to stop solar
operaon. Solar operaon is not
allowed in case Panel temperature
is “ΔT connecon”ºC below tank
temperature