PMEN0602 rev.0 - 05/2023
2
ALARM CODE INDICATION ON REMOTE CONTROL SWITCH
TROUBLESHOOTING
2.1.1 Alarm codes descripon
NOTE
• (o): Opon congurable from Unit controller. This alarm will be displayed if the system has been congured.
• o: Default. This alarm will be displayed in the Unit controller.
• –: No applicable.
Alarm
Code
Retry
Stop
Code
YUTAKI
S/SC
YUTAKI
S80
YUTAKI
M
Origin Detail of Abnormality Main Factors
Alarms generated by PCB
3 - o o o Communicaon Transmission Alarm (Not outdoor unit detected) Loose, disconnected, broken or short-circuited connector
11 - o o o Indoor Water inlet thermistor abnormally (THMwi) Loose, disconnected, broken or short-circuited connector
12 - o o o Indoor Water outlet thermistor abnormally (THMwo) Loose, disconnected, broken or short-circuited connector
13 – o o o Indoor Indoor Liquid Pipe Temp Thermistor Abnormality (THMl) Loose, disconnected, broken or short-circuited connector
14 – o o o Indoor Indoor Gas Pipe Temperature Thermistor Abnormality (THMg) Loose, disconnected, broken or short-circuited connector
15 - (o) (o) (o) Indoor Water Circuit 2 thermistor abnormally (THMwo2) Loose, disconnected, broken or short-circuited connector
16 - (o) (o) (o) Indoor Water DHW thermistor abnormally (THMdhwt) Loose, disconnected, broken or short-circuited connector
17 - (o) (o) (o) Indoor Auxiliary sensor 2 thermistor abnormally (THMaux2) Loose, disconnected, broken or short-circuited connector
18 - (o) (o) (o) Indoor Auxiliary sensor 1 thermistor abnormally (THMaux1) Loose, disconnected, broken or short-circuited connector
19 - o - - Indoor Water Plate HEX pipe thermistor abnormally (THMwohp) Loose, disconnected, broken or short-circuited connector
19 - o - Indoor Sucon R134a pipe thermistor abnormally (THMs) Loose, disconnected, broken or short-circuited connector
23 - o - Indoor Discharge R134a pipe thermistor abnormally (THMd) Loose, disconnected, broken or short-circuited connector
25 - (o) (o) (o) Indoor Auxiliary sensor 3 thermistor abnormally (THMaux3) Loose, disconnected, broken or short-circuited connector
40 - o o o Indoor Incorrect LCD seng Current LCD conguraon does not allow proper operaon
61 - (o) (o) (o) Indoor
No Cascade Messages.
Triggered in case unit is congured to work against cascade control and:
- No messages have been received for 180 seconds.
- No messages have been received from beginning of operaon.
In case this alarm appears, soware stops Indoor and Outdoor operaons unl communicaon is restored.
Loose, disconnected, broken or short-circuited connector
62 - (o) (o) (o) Indoor
Central mismatch.
Triggered in case YUTAKI CASCADE CONTROLLER is congured and they are received central messages or central
control is congured and they are received messages form YUTAKI CASCADE CONTROLLER.
In case this alarm appears, soware stops Indoor and Outdoor operaons unl system is properly congured
Loose, disconnected, broken or short-circuited connector
63 - (o) (o) (o) Communicaon Transmission error between Central and indoor communicaon
Indoor fuse meltdown, Indoor/central connecon wiring (breaking, wiring
error, etc.)
70 P70 o o o Indoor Hydraulic alarm ow & Water Pump malfuncon Water ow is not detected in the hydraulic cycle or Pump defecve
83 P83 o o o Indoor Hydraulic alarm pressure Water pressure is not detected in the hydraulic cycle
72 o - - Indoor Thermostat Heater Alarm High temperature is detected in Electric Heater
73 o o o Indoor Mixing over-temperature limit protecon for Mixed circuit. Circuit 2 supply temperature > Target temperature + oset
74 P74 o o o Indoor Unit over-temperature limit protecon Two > Tmax +5K
75 - o o o Indoor Freeze Protecon by Cold water inlet, outlet temperature detecon
76 - o o o Indoor Freeze Protecon Stop by indoor liquid temperature thermistor
77 - o o o Indoor-LCD Receiver Communicaon failure
No Opentherm/Hlink communicaon for a connuous period of 10
minutes.
78 o o o Indoor-LCD RF Communicaon failure
There is no communicaon for 1 hour with on or two RF receives which
are bound to the RF-Bridge.