OPERATION MODE LOCK SETTING
When the Dip-switch of indoor unit is changed into "Heating mode only" or "Cooli
ng mode only", the
remote controller also needs to be changed into operation mode lock setting. (Refer to Page *73 *)
If the setting of remote controller is not changed , the indoor unit and the remote controller can not
been match.
PROCEDURE
1.
Heating opearation mode lock
While pressing [ECO] button and [POWERFUL] button, simultaneously for about 5
seconds when the remobe controller is OFF.
(1)
(2) Once again "1-(1)" operation , "Heating operation mode lock" is cancelled.
2. Cooling opearation mode lock
10 secondsindicate
ENTER
CANCEL
"LOCK"
Modeselect "Heating" or "Fan" only or "ECO Sleep Timer" or "Filter Cleaning"
(2) Once again "2-(1)" operation , "Cooling operation mode lock" is cancelled.
NOTE :
(1) The indication of "LOCK" and MODE symbols will disappear after 10 seconds.
(2) The OPERATION MODE LOCK setting is memorized even if batterys are exhausted.
Modeselect "Cooling" or "Fan" or "ECO Sleep Timer" or "Filter Cleaning" or "Dehuminify" only
10 secondsindicate
ENTER
CANCEL
"LOCK "
While pressing [ECO] button and [LIGHT ON/OFF] button, simultaneously for about 5
seconds when the remobe controller is OFF.
(1)
132