3 Capacity and selection data
YUTAKI S
TCGB0123 rev.2 - 10/2019
58
3.1 YUTAKI S
3.1.1 Maximum heating capacity table (kW) (Integrated)
Ambient temperature (ºC WB)
-20 -15 -10 -7 -2 2 7 12 15 20 25
System
Water
outlet
temp
(ºC)
CAP
(kW)
IPT
(kW)
CAP
(kW)
IPT
(kW)
CAP
(kW)
IPT
(kW)
CAP
(kW)
IPT
(kW)
CAP
(kW)
IPT
(kW)
CAP
(kW)
IPT
(kW)
CAP
(kW)
IPT
(kW)
CAP
(kW)
IPT
(kW)
CAP
(kW)
IPT
(kW)
CAP
(kW)
IPT
(kW)
CAP
(kW)
IPT
(kW)
RAS-2WHVRP
+
RWM-2.0NRE(-W)
60
3.20 2.29 3.64 2.25 4.00 2.22 5.00 2.17 5.50 1.77 5.66 1.71 5.93 1.61 6.20 1.51
55
4.00 2.42 4.20 2.27 4.48 2.25 4.70 2.24 6.00 2.22 6.30 1.80 6.46 1.68 6.73 1.48 7.00 1.27
50
4.36 2.32 4.60 2.22 4.85 2.13 5.05 2.05 6.15 2.01 6.65 1.71 6.85 1.61 7.17 1.43 7.50 1.25
45
4.00 2.35 4.25 2.30 4.72 2.22 5.00 2.17 5.22 2.00 5.40 1.86 6.30 1.80 7.00 1.63 7.23 1.54 7.62 1.38 8.00 1.23
40
4.15 2.34 4.54 2.24 4.93 2.14 5.17 2.08 5.32 1.86 5.45 1.70 6.40 1.59 7.25 1.48 7.48 1.42 7.87 1.31 8.25 1.21
35
4.30 2.32 4.50 2.14 5.02 2.04 5.33 1.98 5.42 1.73 5.49 1.53 6.50 1.38 7.50 1.34 7.73 1.30 8.12 1.24 8.50 1.18
30
4.50 2.23 4.80 2.09 5.31 1.93 5.62 1.83 5.69 1.65 5.75 1.50 6.70 1.34 7.75 1.30 7.98 1.27 8.37 1.20 8.75 1.14
25
4.70 2.14 5.10 2.04 5.60 1.82 5.90 1.68 5.95 1.56 6.00 1.46 6.90 1.30 8.00 1.27 8.23 1.23 8.62 1.16 9.00 1.09
20
4.90 2.04 5.40 1.99 5.89 1.71 6.18 1.54 6.22 1.48 6.25 1.43 7.10 1.26 8.25 1.24 8.48 1.19 8.87 1.12 9.25 1.05
RAS-2.5WHVRP
+
RWM-2.5NRE(-W)
60
4.00 3.33 4.72 3.27 5.30 3.21 6.20 2.58 6.50 2.24 6.66 2.25 6.93 2.27 7.20 2.29
55
4.70 3.13 5.00 2.94 5.44 2.81 5.80 2.70 7.00 2.64 7.50 2.42 7.73 2.34 8.12 2.21 8.50 2.07
50
5.10 2.97 5.40 2.85 5.90 2.74 6.30 2.66 7.48 2.60 8.00 2.27 8.31 2.22 8.83 2.14 8.75 1.85
45
4.60 2.86 5.00 2.86 5.50 2.80 5.80 2.76 6.36 2.68 6.80 2.62 7.97 2.57 8.50 2.12 8.62 2.01 8.81 1.82 9.00 1.64
40
4.80 2.77 5.27 2.77 5.73 2.71 6.01 2.67 6.51 2.54 6.90 2.44 8.28 2.28 8.85 1.95 9.00 1.84 9.25 1.66 9.50 1.48
35
5.00 2.77 5.40 2.77 5.92 2.65 6.23 2.58 6.66 2.40 7.00 2.26 8.60 2.00 9.20 1.77 9.39 1.67 9.70 1.50 10.01 1.33
30
5.25 2.72 5.70 2.72 6.12 2.53 6.36 2.41 6.82 2.25 7.18 2.12 8.85 1.93 9.50 1.67 9.63 1.59 9.84 1.44 10.05 1.29
25
5.50 2.67 6.00 2.67 6.31 2.40 6.50 2.24 6.97 2.10 7.35 1.99 9.10 1.86 9.80 1.58 9.87 1.50 9.98 1.38 10.10 1.25
20
5.75 2.57 6.30 2.57 6.51 2.32 6.63 2.17 7.13 2.00 7.52 1.87 9.35 1.79 10.10 1.49 10.11 1.42 10.13 1.31 10.15 1.20
RAS-3WHVRP
+
RWM-3.0NRE(-W)
60
5.10 3.64 5.77 3.46 6.31 3.32 7.50 3.21 8.00 2.76 8.12 2.73 8.31 2.70 8.50 2.66
55
5.30 3.53 5.50 3.44 6.42 3.42 7.15 3.40 9.00 3.30 9.80 3.11 9.85 3.07 9.92 3.01 10.00 2.94
50
5.80 3.39 6.08 3.31 6.83 3.24 7.43 3.18 9.15 3.08 9.90 2.91 10.03 2.88 10.24 2.83 10.45 2.78
45
5.25 3.39 5.70 3.35 6.30 3.24 6.67 3.18 7.24 3.06 7.70 2.96 9.30 2.86 10.00 2.70 10.21 2.68 10.55 2.66 10.90 2.63
40
5.63 3.36 6.19 3.27 6.75 3.17 7.08 3.12 7.64 2.96 8.09 2.83 10.15 2.77 10.75 2.60 10.88 2.59 11.09 2.56 11.30 2.53
35
6.00 3.33 6.25 3.29 7.03 3.14 7.50 3.06 8.04 2.85 8.47 2.69 10.99 2.68 11.50 2.50 11.55 2.49 11.62 2.46 11.70 2.44
30
6.25 3.29 6.52 3.23 7.23 3.08 7.65 3.00 8.36 2.77 8.94 2.58 11.15 2.57 11.65 2.32 11.70 2.30 11.77 2.26 11.85 2.22
25
6.50 3.25 6.80 3.16 7.42 3.02 7.80 2.94 8.69 2.68 9.40 2.48 11.30 2.46 11.80 2.15 11.85 2.11 11.92 2.06 12.00 2.00
20
6.75 3.21 7.08 3.10 7.62 2.97 7.94 2.88 9.09 2.62 10.00 2.40 11.50 2.40 12.00 2.00 12.16 1.97 12.43 1.92 12.70 1.87
? NOTE
CAP: Capacity at compressor maximum frequency. Capacity is valid for difference between water inlet and water outlet of 3-8ºC.
IPT: Total input power.
The table above shows the input power (IPT) at maximum capacity (CAP). Most of the time, the unit will run at partial
load, so that the actual input power will be lower.

Table of Contents

Other manuals for Hitachi RAS-2.5WHVRP

Related product manuals