3 Capacity and selection data
YUTAKI M
TCGB0123 rev.2 - 10/2019
63
3
3.3.2 Maximum cooling capacity table (kW)
Ambient temperature (ºC WB)
10 15 20 25 30 35 40 45
System
Water
outlet
temp
(ºC)
CAP
(kW)
IPT
(kW)
EER
(kW)
CAP
(kW)
IPT
(kW)
EER
(kW)
CAP
(kW)
IPT
(kW)
EER
(kW)
CAP
(kW)
IPT
(kW)
EER
(kW)
CAP
(kW)
IPT
(kW)
EER
(kW)
CAP
(kW)
IPT
(kW)
EER
(kW)
CAP
(kW)
IPT
(kW)
EER
(kW)
CAP
(kW)
IPT
(kW)
EER
(kW)
RASM-2VRE
22 7.40 0.95 7.80 6.93 1.03 6.74 6.45 1.11 5.83 5.98 1.19 5.04 5.50 1.26 4.35
18 7.50 0.96 7.80 7.10 0.97 7.30 6.80 1.08 6.30 6.40 1.21 5.30 5.75 1.27 4.54 5.10 1.32 3.85
15 7.00 0.97 7.20 6.92 0.99 7.02 6.83 1.00 6.84 6.75 1.01 6.67 6.27 1.10 5.68 5.79 1.19 4.84 5.31 1.29 4.13 4.83 1.38 3.50
10 6.80 0.97 7.00 6.58 1.01 6.54 6.37 1.04 6.12 6.15 1.08 5.72 5.71 1.17 4.86 5.26 1.27 4.14 4.82 1.37 3.52 4.37 1.47 2.98
7 6.20 0.98 6.30 6.10 1.03 5.94 6.00 1.07 5.60 5.80 1.12 5.20 5.40 1.23 4.40 5.00 1.33 3.75 4.55 1.43 3.19 4.10 1.52 2.70
5 5.50 1.08 5.10 5.20 1.17 4.46 4.90 1.26 3.90 4.60 1.34 3.42 4.30 1.43 3.00 4.00 1.52 2.63 3.70 1.61 2.30
RASM-3VRE
22 10.50 1.67 6.30 9.90 1.73 5.72 9.30 1.80 5.17 8.70 1.86 4.67 8.10 1.93 4.20
18 10.60 1.64 6.45 10.20 1.71 5.95 9.50 1.84 5.15 9.00 1.94 4.65 8.00 1.98 4.04 7.00 2.03 3.45
15 9.50 1.40 6.80 9.52 1.52 6.26 9.55 1.65 5.80 9.57 1.77 5.40 8.86 1.87 4.75 8.15 1.96 4.16 7.44 2.05 3.63 6.73 2.14 3.14
10 8.80 1.44 6.10 8.71 1.58 5.50 8.62 1.73 4.99 8.53 1.87 4.56 7.96 1.99 4.01 7.40 2.10 3.52 6.84 2.22 3.08 6.27 2.33 2.69
7 8.10 1.56 5.20 8.03 1.68 4.78 7.97 1.80 4.42 7.90 1.93 4.10 7.60 2.05 3.70 7.00 2.19 3.20 6.50 2.32 2.80 6.00 2.45 2.45
5 8.00 1.74 4.60 7.68 1.86 4.12 7.35 1.99 3.70 7.03 2.11 3.33 6.70 2.23 3.00 6.15 2.45 2.51 5.60 2.67 2.10
? NOTE
CAP: Capacity at compressor maximum frequency. Capacity is valid for difference between water inlet and water outlet of 3-8ºC.
IPT: Total input power.