EasyManua.ls Logo

Hitachi RAS-24MH1 - MAIN PARTS COMPONENT; THERMOSTAT (Room Temperature Thermistor); INDOOR FAN MOTOR; OUTDOOR FAN MOTOR

Hitachi RAS-24MH1
92 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
– 30 –
MAIN PARTS COMPONENT
THERMOSTAT (Room Temperature Thermistor)
Thermostat Speci cations
INDOOR FAN MOTOR
Fan Motor Speci cations
CONNECTION
TEMPERATURE
°C (°F)
INDICATION
16
INDICATION
24
INDICATION
32
MODEL RAS-24MH1
THERMOSTAT MODEL IC
OPERATION MODE COOL HEAT
ON 15.6 (60.1) 20.0 (68.0)
OFF 15.3 (59.5) 20.7 (69.3)
ON 23.6 (74.5) 28.0 (82.4)
OFF 23.3 (73.9) 28.7 (83.7)
ON 31.6 (88.9) 36.0 (96.8)
OFF 31.3 (88.3) 36.7 (98.1)
MODEL
RAS-24MH1
POWER SOURCE DC: 263 ~ 400V
OUTPUT
38W
(Control circuit built in)
BLU : BLUE YEL : YELLOW BRN : BROWN WHT : WHITE
GRY : GRAY ORN : ORANGE GRN : GREEN RED : RED
BLK : BLACK PNK : PINK VIO : VIOLET
COIL
MODEL
RAC-24MH1
POWER SOURCE DC: 120 ~ 380V
OUTPUT (W) MAX 47
OUTDOOR FAN MOTOR
Fan Motor Speci cations
ITEM
RESISTANCE VALUE ( )
20°C 2M U-V 35 ± 2.5 V-W 35 ± 2.5 W-U 35 ± 2.5