Loading...
Monobloc system - R32 YUTAKI M
Model
Power
supply
Applicable
voltage
Operation mode
MC
(A)
CB
(A)
ELB
(nº of poles/A/mA)
U max.
(V)
U min.
(V)
RASM-2VRE
1~ 230V
50Hz
253 207
Without DHW tank heater 10.6 16
2/40/30
With DHW tank heater 23.1 32
RASM-3VRE
Without DHW tank heater 16.0 20
With DHW tank heater 28.5 32
? NOTE
The data corresponding to DHW tank heater is calculated in combination with the domestic hot water tank accessory “DHWT-(200/300)S-3.0H2E”.