6 Optional functions
186
SMGB0087 rev.0 - 12/2013
Element Optionalfunction
Individual
setting
Settings Settingconditions Description
F1
PC-ARF: Automatic
OFF timer setting
X
00
Not activated
function
This function is used to set the automatic
timer to switch off when the unit has
been started by remote control.
Do not set the functions "0C"-"0F" when
two remote control switches are used in
the seame remote control group.
01 1 h
02 2 h
03 3 h
04-24 (04-24) h
0A 30 min
0B 90 min
0C 40 min
0D 45 min
0E 50 min
0F 55 min
PC-ART: Not
available
– 00-0B Not available –
F2
Remote control
main-sub setting
X
00 Main
This function is used when two remote
controls are installed in a system.
01 Sub
F3
PC-ARF: Automatic
reset of setting
temperature
(4)
X
00
Not activated
function
This function releases the xed tempera-
ture setting after a certain time to limit
unit operations and save energy.
01 Activated function
PC-ART: Not
available
– 00-01 Not available –
F4
PC-ARF: Automatic
reset time
X
00
30 minutes
(factory setting)
This function is used to set the automatic
reset time with the temperature setting
01 15 minutes
02 60 minutes
03 90 minutes
PC-ART: Not
available
– 00-03 Not available –
F5
PC-ARF: Automatic
reset temperature for
cooling
X
19 19 °C
This function is used to set automatic
temperature reset in FAN/COOL/DRY
modes.
20 20 °C
21-24 (21-24) °C
25
25 °C
(factory setting)
26-28 (26-28) ºC
29 29 ºC
30 30 ºC
PC-ART: Not
available
– 19-30 Not available –