10 Servicing
379
SMGB0087 rev.0 - 12/2013
10
10.4.9 Opening electrical box (P plate)
1 Remove the service cover following “10.4.1Removingservicecover”
in this chapter.
2 Unplug all the connectors of the electrical box.
3 Remove 5 screws which x the electrical box and open the P plate
turning counter clockwise approximately 90°.
• Check that the LED201 (red) on the inverter PCB (PCB2) is OFF.
Upper cover
Power plate
Fixing
screw
2 Fixing
screws
2 Fixing
screws
10.4.10 Removing Reversing valve coil
1 Remove the service cover, the bottom service cover, the rear cover and
the upper cover following “10.4.1Removingservicecover”, “10.4.4Re-
movingthebottomservicecoverandrearcover” and “10.4.3Removing
uppercover”. Disconnect the PCN100 connector on the control PCB of
the electrical box.
2 Remove 1 xing screw to remove the reversing valve coil.
3 When reassembling, perform the procedure in the reverse way of re-
moving.
Reversing valve
Fixing screw for
Reversing valve
N O T E
Fixthewiresbyplasticbandstotheoriginalposition.
10.4.11 Removing electronic expansion valve coil
1 Remove the service cover, the bottom service cover
and the rear cover following “10.4.1Removingservice
cover” and “10.4.4Removingthebottomservicecover
andrearcover”.
2 Disconnect the CN5A connector on the control PCB of
the electrical box.
3 Hold the coil of the expansion valve and pull out upward.
It is easier to remove the expansion valve coil if it is ro-
tated while pulling it upward.
4 When reassembling after replacing the expansion valve
coil, perform the procedure in the reverse way of remo-
ving. The expansion valve coil is equipped with a lock
mechanism. After attaching the expansion valve coil,
rotate it until the sound of locking is heard.
N O T E
Fixthewiresbyplasticbandstotheoriginalposition.