Refrigerant piping & refrigerant charge14
14.3.3  Refrigerant piping selection
Select the piping connection sizes according to the following pro-
cedures
•  Between outdoor unit and branch pipe: Select the same pipe 
connection size as the pipe size of the outdoor unit.
•  Between branch pipe and indoor unit: Select the same pipe 
connection size as the pipe size of the indoor unit.
1 indoor unit system
(mm)
Outdoor Unit HP
Pipe Size (L)
Gas Liquid
2 / 2.5 Ø12.70 Ø6.35
3 Ø15.88 Ø9.52
2 indoor units system
(mm)
Outdoor 
Unit HP
Pipe Size (A) Multi-kit
Gas Liquid IVX Series
ES 
series
2 / 2.5 Ø12.70 Ø6.35 TE-03N1 -
3 Ø15.88 Ø9.52 TE-03N1
Pipe connection size after branch pipe
(mm)
Indoor Unit capacity
Pipe Size (B, C)
Gas Liquid
≤ 1.5 HP Ø12.70 Ø6.35
1.8 / 2.0 HP Ø15.88 Ø6.35
14.3.4  2 indoor units system installation
 
Height difference between indoor units and distributor
It is recommended to install all indoor units at the same height. 
When the height difference between the indoor units due to buil-
ding construction is necessary, this should be less than the value 
indicated in the table. 
ื
10m (IVX-P)
3m
0.5m
(IVX-C)
(ES)
ืืืื
ื
30m
IU1
IU2
OU1
OU1
ื
3m (ES ืP
ื
3m (ES ืP
 
Installing Distributor
1  Selecting the distributor
Install the distributor supplied by HITACHI on request the T-joint 
can not be installed instead of a branch pipe.
2  Installing the distributor
Fix the branch pipe horizontally to the pillar, wall or ceiling. Piping 
must  not  be  xed  rigidly  to  the  wall  as  thermal  expansion  and 
contraction can cause pipe fracture.
Horizontal
To  indoor 
unit
To outdoor unit
Vertical
To indoor unit
Fixing  the  branch  pipe  to 
the surface of pillar or wall
Horizontal
Horizontal
Fixing the branch pipe to 
ceiling or beam
  NOTE
Fix the piping from outside of insulation or inserting absorber bet-
ween the pipe and a xing metal.
3  Correct position of twin distributor
•  This is the correct position of twin branch pipe:
Greater 
than 0.5 m
Main pipe
Refrigerant 
direction
Up
Branch pipe
Main pipe
Refrigerant  
direction
Down
•  This is wrong position:
Main pipe
Refrigerant direction
Branch pipe
Branch pipe
Refrigerant 
direction
Main pipe
Branch pipe
14.3.5  Connecting are adapter
Flare nut (accessories)
Pipe (accessories)
Indoor unit
Flare adapter (accessories)
Gas line
Pipe  
(eld  
supplield)
Liquid line
The  piping  sizes  for  indoor  unit  and  outdoor  unit  are  different. 
Attach the are adapter (accessories) at the indoor piping union 
part.
Use the adequate are adapter as follows:
Indoor unit
Flare adapter
Gas pipe Liquid pipe
2.0 HP
Big size 
(∅15.88→∅12.70)
-
2.5 HP
Big size 
(∅15.88→∅12.70)
Small size 
(∅9.52→∅6.35)