CAUTION
•  Do not charge  OXYGEN, ACETYLENE,  or other ammable 
and poisonous gases into the refrigerant because an explo-
sion can occur. It is recommended that oxygen free nitrogen 
be charged for these types of tests cycle when performing 
a leakage test or an airtight test. These types of gases are 
extremely dangerous, 
•  Insulate  the  unions  and  are-nuts  at  the  piping  connection 
part completely.
•  Insulate the liquid piping completely to avoid a decrease of 
performance; if not, it will cause sweating on the surface of 
the pipe.
•  Charge refrigerant correctly. Overcharging or insufcient char-
ging could cause a compressor failure.
•  Check for refrigerant leakage in detail. If a large refrigerant 
leakage occurred,  it would cause  difculty with breathing  or 
harmful  gases  would  occur  if  a  re  were  being  used  in  the 
room. 
•  If  the  are  nut  mut  is  tigthened  too  hard,  the  are  nut  may 
crack after a long time and cause refrigerant leakage.
 
Evacuation and refrigerant charge
Evacuation and refrigerant charging procedure should be perfor-
med according to the following instructions.
The stop valve has been closed before shipment. However, make 
sure that the stop valves are closed completely.
 - Connect  the  indoor  unit  and  the  outdoor  unit  with  eld-
supplied refrigerant piping.
 - Connect the gauge manifold using charging hoses with a 
vacuum pump or a nitrogen cylinder to the check joints of 
the liquid line and the gas line stop valve.
 - Check for any gas leakage at the are nut connection, by 
using nitrogen  gas to  increase the pressure at 4.15MPa 
for outdoor units inside of the eld-supplied piping.
 - Operate the vacuum pump for 1 to 2 hours until the pres-
sure  decreases  lower  than  a  pressure  of  756  mmHg  in 
vacuum.
 - For  charging  refrigerant,  connect  the  gauge  manifold 
using charging hoses with a refrigerant charging cylinder 
to the check joint of the liquid line stop valve.
 - Charge  the  proper  quantity  of  refrigerant  according  to 
the piping length (Calculate the quantity of the refrigerant 
charge).
 - Fully open the gas line stop valve, and slightly open the 
liquid line stop valve.
 - Charge refrigerant by opening the gauge manifold valve.
 - Charge the required refrigerant within the difference range 
of ±0.5kg by operating the system in cooling.
 - Fully open the liquid line stop valve after completing refri-
gerant charge.
 - Continue  cooling  operation  for  more  than 10  minutes  to 
circulate the refrigerant. 
 - Remove the “close” plate from the stop valve and hook the 
attached “Open” plate at the stop valve.
Gas line
Liquid line
Liquid stop valve
Gas stop valve
Nitrogen tank
(For air tight test & nitrogen blow 
during brazing)
Vacuum cylinder
Manifold 
gauge
Outdoor unit
Example of Evacuation and Refrigerant Charge for HVN(P/C)1
14
14.4 REFRIGERANT CHARGE
When the pressure is measured, use the check joint of gas stop 
valve, and use the check joint of liquid piping in the gure below.
At  that  time,  connect  the  pressure  gauge  according  to  the  fo-
llowing table because of high pressure side and low pressure side 
changes by operation mode.
Cooling  
Operation
Heating  
Operation
Check Joint for Gas Stop Valve Low Pressure High Pressure
Check Joint for Liquid Stop Valve
Exclussive for Vacuum Pump 
and Refrigerant Charge
  NOTE
Be careful that refrigerant and oil do not splash to the electrical 
parts at removing the charge hoses.
Stop valve (liquid)
Stop valve (gas)
14.5 CAUTION OF THE PRESSURE BY CHECK JOINT