Test running18
Remote control switch 
indication
Unit condition Wrong portions
Inspection points after power source 
OFF
The operation lamp 
ickers. (1 time/1 sec.) 
and the unit number and 
alarm code 03 icker.
The unit does not start.
The power source of 
outdoor unit in not turned 
ON.
The connecting wires of 
operating line are inco-
rrect or loosened.
1  Connecting  order  of  each  terminal 
boards. 
2  Screw  fastening  of  each  terminal 
boards.
  NOTE
Recovering method of FUSE for opera-
ting circuit.  There  is  a fuse (FUSE4 on 
indoor unit  PCB1,  EF1 on  outdoor unit 
PCB1) to protect operating circuit on the 
PCB, when the power lines are connec-
ted to operating lines. If fuse is melted, 
operating circuit can be recovered once 
by setting the dip switch on the PCB as 
shown in 
The operation lamp ic-
kers. (1 time/2 sec.)
The unit does not start.
Remote control cable is 
broken.
Contact of connectors is 
not good.
The connection of remote 
control cable is incorrect
This is the same as item  1 and 2
Indication of icker ex-
cept above
The unit does not start, or start once and 
then stops
The connection of 
thermistor or other con-
nectors are incorrect. 
Tripping of protector 
exists, or else.
Check by the abnormality mode table in 
the Technical Catalogue (Do it by servi-
ce people).
The operation lamp 
ickers. (1 Time/1s)
Unit number , alarm 
code  and unit code 
 icker
The unit does not start.
The connection of the 
remote control cable 
between indoor units is 
incorrect.
Check by the abnormality mode table in 
the Technical Catalog (Do it by service 
people).
Back to  after checking
Instructions for the recovery when the fuse of the transmission circuit is blown out:
1  Correct the wiring to the terminal board.
2  Set pin 2 of DSW7 on the indoor units PCB to ON
18.2 TEST RUN PROCEDURE FROM OUTDOOR UNIT SIDE
The procedure of test run from outdoor unit side is indicated below. Setting of this DIP switch is available with the power source ON.
Setting of Dip switch
DSW301
Switch for setting of service operation and function
Factory 
setting
1  Test Run
2  COOL/HEAT 
(Setting ON: Heat Operation)
3  OFF (Fixed)
4  Manual Compressor stop
5  OFF (Fixed)
6  OFF (Fixed)
  CAUTION
•  Do not touch any other electrical parts when operating swit-
ches on the PCB.
•  Do not attach or detach service cover when the power source 
for the outdoor unit is ON and the outdoor unit is operated.
•  Turn all DIP switches of DSW301 OFF when the test run ope-
ration is completed.