The following table shows the air flow rate setting using the remote control and the actual air flow rate of the total heat
exchanger when this function is enabled.
Settings Condition setting
00 Not available
01 Available
Air flow rate setting with the remote control Air flow rate on the total heat exchanger
Low Medium
Medium Height
Height Height
E3 – Not used
Settings
Condition setting
00 Not available
01 Used as setting for conditions 00
E4 – Pre-cooling / pre-heating period
KPI: This function is useful to delay start-up of the total heat exchanger. The setting condition and delay time are shown
below:
Setting
Start-up delay time
00 0 minutes (standard)
01 30 minutes
02 60 minutes
Econofresh kit: This function is useful to set the gas sensor input. The setting condition and delay time are shown below:
Setting
Gas sensor Contents
00 Standard The gas sensor input is not available.
02 CO
2
 sensor The gas sensor input is available.
E5 – Not used
Settings
Condition setting
00 Not available
01 Used as setting for conditions 00
E6 – Fan operating time after stoppage of the indoor unit in cooling mode
This prevents condensation from accumulating in the unit by keeping the fan running after it is switched off.
Settings
Condition setting
00 Not available
01 60 minutes
02 120 minutes
E7 – Not used
E8 – Fan operating control after stoppage of the indoor unit in heating mode
This function is useful to avoid the perception of cold draughts by reducing the indoor fan speed with the heating thermostat
off.
Setting condition
Fan operation with the thermostat switched off
00 Not available
01 Available