8.3 Procedure for checking fan motors in indoor units
Name and abbreviation of the cable colours used:
Black Brown Red Yellow Green Blue Grey Orange White
BLK BRN RED YEL GRN BLU GRY ORN WHT
Indoor units
Power
input
Wiring diagram Cable no.
Resistance (Ω)
RCI-1.0FSN2E
RCI-1.5FSN2E
RCI-2.0FSN2E
RCI-3.0FSN2E
56 W DC motor
RCI-4.0FSN2E
RCI-5.0FSN2E
RCI-6.0FSN2E
108 W DC motor
RCIM-1.0FSN2
RCIM-1.5FSN2
RCIM-2.0FSN2
52 W DC motor
RCD-1.0FSN2
RCD-1.5FSN2
RCD-2.0FSN2
35 W
BLK1-3RED
RED3-5WHT
159.00
92.00
to 20 °C
RCD-2.5FSN2
RCD-3.0FSN2
55 W
BLK1-3RED
RED3-5WHT
70.90
81.70
to 20 °C
RCD-4.0FSN2 35 W x 2
BLK1-3RED
RED3-5WHT
159.00
92.00
to 20 °C
RCD-5.0FSN2 55 W x 2
BLK1-3RED
RED3-5WHT
70.90
81.70
to 20 °C
RPC-2.0FSN2E
RPC-2.5FSN2E
RPC-3.0FSN2E
65 W
BLK1-2RED
RED2-3YEL
YEL3-4GRY
GRY4-5BLU
RED2-6WHT
59.90
16.90
15.80
15.80
63.60
to 20 °C