RCD - 2-way cassette type
  D A N G E R
Wear gloves to avoid injuries when handling components.
Work prior to cleaning
Turn off the power supply switches before starting maintenance work and fit the appropriate safety locks and warnings.
Wait 5 minutes after turning off the power supply switches.
Place a vinyl sheet on the floor to protect the furniture and other items from the cleaning water.
Remove the following components:
1 Drain pan.
2 Float switch.
3 Drain mechanism.
Cleaning the indoor unit
Clean the drain pan you have just removed.
Use a brush to clean any dust from the interior surface of the heat
exchanger  and  from  the  fins  on  the  inlet  side.  To  do  so,  brush
downwards and collect all of the dust in a bucket or cardboard box.
Place  a  vinyl  sheet  around  the  heat  exchanger  to  prevent  the
cleaning  water  from  splashing  the  insulation  surface  and  drain
pump.
Attach  the  vinyl  sheet  to  the  side  plate  of  the  exchanger  using
adhesive tape. Seal the gap between the vinyl sheets with adhesive
tape.
12 Maintenance notes
372