TCI-20007-rev.1
i
IMPORTANT NOTICE
● HITACHIpursuesapolicyofcontinuingimprovementindesignandperformanceofproducts.
Therightisthereforereservedtovaryspecicationswithoutnotice.
● HITACHIcannotanticipateeverypossiblecircumstancethatmightinvolveapotentialhazard.
● Thisheatpumpairconditionerisdesignedforstandardairconditioningonly.Donotusethisheatpump
airconditionerforotherpurposessuchasdryingclothes,refrigeratingfoodsorforanyothercoolingor
heatingprocess.
● Donotinstalltheunitatthefollowingplaces.Itmaycauseare,deformation,corrosionorfailure.
*Placeswhereoil(includingmachineryoil)maybepresentinquantities.
*Placeswherealotofsuldegasdrifts,suchashotsprings.
*Placeswhereinammablegasmaybegeneratedorow.
*Placeswherestrongsaltywindblows,suchascoastregions.
*Placeswithanatmosphereofacidityoralkalinity.
● Donotinstalltheunitintheplacewheresilicongasdrifts.Ifthesilicongasattachestothesurfaceofthe
heatexchanger,thensurfacerepelswater.Asaresult,drainwatersplashesoutsideofthedrainpan
andsplashedwaterrunsinsideoftheelectricalbox.Intheend,waterleakageorelectricaldevices’failure
mayoccur.
● Payattentiontothefollowingpointswheninstallingtheunitinahospitalorotherfacilitieswhere
electromagneticwavesaregeneratedfrommedicalequipment.
*Donotinstalltheunitintheplacewhereelectromagneticwavesaredirectlyradiatedtotheelectricalbox,
controllercableorwiredcontroller.
*Installtheunitatleast3metersawayfromdevicesgeneratingelectromagneticwaves,suchasaradio.
● Donotinstalltheunitintheplacewhereanimalsandplantscatchthedirectoutletair.Itcouldadversely
a󰀨ectanimalsandplants.
● Theinstallerandsystemspecialistshallsecuresafetyagainsttherefrigerantleakageaccordingtothe
localregulationsorstandards.Thefollowingstandardsmaybeapplicable,ifthelocalregulationsarenot
available;
InternationalOrganizationforStandardization,ISO5149orEuropeanStandard,EN378orJapanStandard,
KHKS0010.
● Nopartofthismanualmaybereproducedwithoutwrittenpermission.
● ItisassumedthatthisheatpumpairconditionerwillbeoperatedandservicedbyEnglishspeakingpeople.
Ifthisisnotthecase,thecustomershouldbeprovidedwithsafety,cautionandoperatingsignsinthe
nativelanguage.
● Ifyouhaveanyquestions,contactyourdistributorordealerofHITACHI.
● Thismanualgivesacommondescriptionandinformationforthisheatpumpairconditionerwhichyou
operateaswellforothermodels.
● Thisheatpumpairconditionerhasbeendesignedforthefollowingtemperatures.Operatetheheatpump
airconditionerwithinthisrange.
● Thismanualshouldbeconsideredasapermanentpartoftheairconditioningequipmentandshould
remainwiththeairconditioningequipment.
Temperature
(
o
C)
Maximum Minimum
Cooling
Operation
Indoor 30 DB 21.5 DB
Outdoor 43 DB* -5 DB*
Heating
Operation
Indoor 25 DB 17 DB
Outdoor 15.5 WB* -10 WB*
DB:DryBulb,WB:WetBulb
*Thetemperaturemaychangedependingontheoutdoorunit.