CONTROL SYSTEM
1-74 
TCI-20007-rev.1
< Indoor Unit >
Model
RPC-1.5FSR, RPC-2.0FSR, RPC-2.5FSR, RPC-3.0FSR,
RPC-4.0FSR, RPC-5.0FSR, RPC-6.0FSR
 For Evaporator Fan Motor
Internal Thermostat Automatic Reset, Non-Adjustable (each one for each motor)
Cut-Out
o
C -
Cut-In
o
C -
Chip Ceramic PTC
Thermistor
o
C 100
For Control Circuit
  Fuse Capacity A 5
 Freeze Protection
Thermostat Cut-Out
o
C 0
Cut-In
o
C 11
Thermostat
Dierential
o
C 2
10.4  Protection and Safety Control
Compressor Protection
The compressor is protected by the following 
devices and their combinations.
High Pressure Switch  - This switch cuts out the 
operation of the compressor when the discharge 
pressure exceeds the setting.
Crankcase Heater - This band type heater protects 
against oil Carry-over during cold starting, as it is 
energized while the compressor is stopped.
Chip Ceramic
PTC Thermistor (POSISTOR 
R
) in the DC fan 
motor controls the fan motor revolution when the 
fan motor internal temperature exceeds the setting.
10.5  Safety and Control Device Setting