A10762300A-rev.1
17
(9) Donottouchtherefrigerantpipestolow
strengthportionsofwallsorceilings.Ifnot,
itmaycauseabnormalsoundorvibration.
(10) Performtheairtighttest.Theairtight
proceduresshouldbeperformedaccording
to“Installation&MaintenanceManual”ofthe
outdoorunit.
(11) Insulateeachareconnectionwithoutgap
topreventofdewcondensationbyusing
theaccessoryinsulations,andinsulateeach
refrigerantpipealso.
(6) Whenon-sitepipingwithjointsuchaselbow,
socketisburied,provideaserviceaccess
doortofacilitatethecheckforconnecting
part.
(7) Performtosupportforearthquakeresistant
tothepipesinordernottodamagebyan
externalforce.
(8) Donotclamptightlytherefrigerantpipe
whensupportingforpreventionofheat
stress.
(12) Whenthethicknessofinsulationforgas
pipingis20mm,attachtheinsulationmoving
totheindoorunitsideasshownintheright
gure.
Whenattaching,wraptheinsulationwithout
gapbetweentheinsulationandlocalpiping
insulation.
● Do not apply excessive force to the are nut
when tightening. If applied, the are nut may
crack due to aged degradation and refrigerant
leakage may occur.
Use the specied tightening torque.
● Make sure that a refrigerant leak test has
been performed. Refrigerant (Fluorocarbon
or Diuoromethane) for this unit is non-
toxic, and odorless. If the refrigerant should
somehow escape and come into contact with
ame, toxic gas will form. This gas is heavier
than air and will settle near oor areas and
spread where it can cause suocation to
those nearby. In addition, diuoromethane is
ammable and can cause re.
● Captheendofthepipewhenthepipeistobe
insertedthroughahole.
● Captheendofthepipetoavoidrainorwater
entering.
● Donotputpipesonthegrounddirectlywithouta
caporvinyltapeattheendofthepipe.
(14) Evacuationandrefrigerantcharging
proceduresshouldbeperformedaccording
to“Installation&MaintenanceManual”ofthe
outdoorunit.
(13) Ifusingaformingagent(recommended
Gupoex)afterinstallingtheairinletgrille,
avoidtouchingtheformingagenttotheair
inletgrille.Iftheformingagentistouchedto
theairinletgrille,itmaycausethebreakage
andthefallingoftheairinletgrille.Inthis
case,completelywipeothetouched
formingagent.
Fasten 3 places of
the pipe by cord clamps
(Accessory).
Fix the vinyl tape position at the vertical part
(Insulation for Refrigerant Pipe (Accessory)).
Fasten securely cord clamps and
the vinyl tape in order to prevent
the pipe from dew condensation
Unit
Side
Check no clearance between
the indoor unit and the insulation.
Insulation Material
(Factory-Supplied)
Insulation for
Refrigerant Pipe
(Field-Supplied)
Refrigerant Pipe
(Field-Supplied)
Refrigerant Pipe
(Field-Supplied)
Insulation (Attached to Indoor Unit)
Wrap tape without gap.
Indoor Unit
Insulation for Refrigerant Pipe
(Field-Supplied)