A10762300A-rev.1 
29
7.3 PositionofElectricalWiringConnection
● Tightly secure wirings to the terminal 
block according to the specied torque.  If 
tightening the terminals is not completed, 
heat generation, an electric shock or a re 
will occur at the terminal connection.
● Make sure that the wires are securely xed 
in order not to apply an external force to the 
terminal connection of the wirings.  If xing is 
not completed, heat generation or a re will 
occur.
• Theelectricalwiringconnectionfortheindoor
unitisshownintheitem7.2.2.
• Theconnectionattheterminalblockforthe
indoorunitisshowninthegurebelow.Check
theoutdoorunitforthecombinationbeforethe
wiringwork.Thescrewsattheterminalblock
shouldbeperformedaccordingtothetightening
torqueasshowninthetablebelow.
(1) Connectthecablefortheoptionalwired
controllerortheoptionalextensioncable
totheterminalsinsidetheelectricalbox
throughtheconnectingholeinthecabinet.
(2) Connectthepowersupplyandtheearth
wirestotheterminalsintheelectricalbox.
(3) Connectthewiresbetweentheindoorunit
andtheoutdoorunittotheterminalsinthe
electricalbox.
(4) Connectcablescorrectlytomatchthe
terminalNo.andthemarkband.
(5) Connectthetransitionwiresbetweenindoor
unitsconnectedtothesameoutdoorunit.
(6) Donotconnectthemainpowersource
cablestothecontrolline(TerminalsA,B,
1and2ofTB2).Ifconnected,theprinted
circuitboard(PCB)willbebroken.
(7) Tightlyclampthewiresusingthecordclamp
insidetheelectricalbox.
(8) Standardcompliancewheninstallingtheunit
inAustralia.
(a) Connectthebothendsofshieldedtwist
paircable(controllercableandcontrol
cable)totheearthasshownbellow.
TighteningTorqueforTerminals
TighteningTorque
M4 1.0 - 1.3 (N-m)
TerminalBlockfor
PowerSourceCable
TB1(black)
TerminalBlockfor
ControlCable
TB2(white)
● Donotconnectthemainpowersourcecablesto
thecontrolline(TerminalsA,B,1and2ofTB2).
Ifconnected,theprintedcircuitboard(PCB)will
bebroken.
● Payattentiontofollowingswhenwiresare
connectedtoterminalblock.
(A) Attachaninsulationtapeorasleevetoeach
terminal.
(B) Maintainthedistancebetweentheelectrical
boxandtheterminalstopreventashort
circuit.
(C) Maintainthedistancebetweentheterminals.
(b) Alockableisolatorshallbemounted
adjacenttobutnotontheunitandwill
disconnectallactiveconductorstotheunit
fromthesupplycircuit.
-
S/NR/L1
AB
Shielded Twist Pair Cable
Shield
(A)
(B)
Screw