7.5 WiringConnection
(1) Thewiringconnectionfortheindoorunitis
showninthegurebelow.
(2) Thewiringconnectionforelectricalboxisas
follows.
(a)Opentheairinletgrille.
(b)Removetheelectricalboxcover.
(c) Connectthecontrolcable,powersource
cableandcontrollercable.
7.6 DipSwitchesSetting
(1) TurnOFFallthepowersupplyoftheindoor
unitandtheoutdoorunitbeforeDipSwitch
setting.Ifnot,thesettingisinvalid.
(2) ThepositionsofDipSwitchesonPCBare
showninthegurebelow.
Tightly clamp wires by the cord clamp after the 
wiring is completed to the terminal block.  If not 
completed, it may cause a re by biting wires.
(d) Afterthewiringiscompleted,attachthe
electricalboxcoveragainwithcarein
ordernottobitewires.
Cap
Wire Connection
Rear Side
Cap
Wire Connectio
PCB1
Controller Cable
(White)
Terminal Block
(Black)
Power Source
Line
Earth Terminal
A B 1 2
Terminal Block
(White)
Controller
Cable
Transition Wiring
Between Indoor Units
Control
Cable
(Case that multiple indoor units are
operated by one wired controller.)
This is not required for the simultaneous
operation of UTOPIA series at a maximum
of 4 indoor units.
(3) UnitNo.Setting(RSW2&DSW6) 
TheindoorunitNo.ofallindoorunitsarenot
required.Theindoorunitnumbersaresetby
theauto-addressfunction.Iftheindoorunit
numbersettingisrequired,settheunitNo.
ofallindoorunitsrespectivelyandseriallyby
followingsettingposition.Itisrecommended
thattheunitnumbersettingstartfrom“1”.
DSW4
DSW9
DSW7
DSW5
DSW6
RSW1
RSW2
DSW3
SW1
(Unit Model Code Setting)
RSW1 & DSW5
(Refrigerant Cycle No. Setting)
DSW9
(Optional Function Setting)
RSW2 & DSW6
(Indoor Unit No. Setting)
DSW3
(Capacity Setting)
DSW7
(Fuse Recover)
Indoor Unit PCB
1 2 3 4 5 6
ON
OFF
1 2 3 4 5 6
ON
OFF
DSW6 (Tens Digit)
RSW2 (Units Digit)
Setting
Position
Set by inserting
slotted screwdriver
into the groove.
Ex.) Set at No.16 Unit
DSW6
RSW2
Set No.1 Pin at ON side
Set at "6"
3
4
1
0
8
9
2
5
6
7
3
4
1
0
8
9
2
5
6
7
Before shipment, DSW6 and RSW2 are set at "0".
(a) for Units Supporting H-LINK II
     The unit Nos. can be set for Max. 64 indoor units
     (No.0~63).
(b) for Units Supporting H-LINK
     The unit Nos. can be set for Max. 16 indoor units
     (No.0~15).