A10762300A-rev.1 
41
3)Iftheindicatednumberisnotequalto
theactualconnectednumberofindoor
units,theauto-addressfunctionisnot
performedcorrectlyduetoincorrect
wiring,electricnoise,etc.TurnOFF
thepowersupply,andcorrectthewiring
aftercheckingthefollowingpoints;(Do
notrepeatturningONandOFFwithin
10seconds.)
*PowerSupplyforIndoorUnitisNot
TurnedONorIncorrectWiring.
*IncorrectConnectionofConnecting
CablebetweenIndoorUnitsor
IncorrectConnectionofController
Cable
*IncorrectSettingofRotarySwitchand
DipSwitch(Thesettingisoverlapped.)
ontheIndoorUnitsPCB
4)Press“
On/O”tostartthetestrun.
5)Press“
”andseteachitem.
(b) Press“
On/O”. 
Startthetestrunwhenindicatingtheair
owvolume“HIGH”(defaultsetting)and
lighttheoperationlamp.Atthistime,
2-hourOFFtimerwillbesetautomatically.
2)Thetotalnumberoftheindoorunits
connectedisindicatedontheLCD
(Liquidcrystaldisplay).Thecaseofthe
twincombination(one(1)setwithtwo
(2)indoorunits)isindicated“2units”,
andthetriplecombination(one(1)set
withthree(3)indoorunits)isindicated“3
units”.
“A”
(c) Checktoensurethatthemotionsensoris
operatedcorrectlyasfollowingprocedures
(inthecaseofthelowercoverwiththe
motionsensor).
1)Pressandhold“Menu”and“Back/Help”
simultaneouslyforatleast3seconds
duringthetestrunmode.Thecheck
menuscreen“A”isdisplayed.
Back
Adj.Sel. ON Rtrn
Test Run Setting: 2 units
MODE
SPEED
AUTO
COOL
Adj.Sel. OFF
Test Run: 2 units
MODE
SPEED
AUTO
COOL
LOUV.
Test Time 120min
Check Menu
Function 5
Model Display
Alarm History Display
Check 2
01
/
02
Check 1
Sel. Entr Rtrn
OK Back
2)Select“Check1”atthecheckmenu
andpress“OK”.(screen“B”willbe
displayed.)
 (ThisscreenisNOTdisplayedwhen
thenumberofindoorunitconnected
withthewiredcontrolleris1(one).In
thiscase,screen“C”willbedisplayed.)
3)Selecttheindoorunitbypressing 
“
”andpress“OK”.Thecheck
datascreen“C”willbedisplayed.
“B”
“C”
Model Display:01-02  Model:F .08
01-01
01-02
01-03
01-04
IDU  : 
******
  S/N:000000
ODU  : 
******
  S/N:000000
Check 1:01-03
01
/
07
Next Page
Rtrn
q1  50
P2  10
P1  00
L4  00
Item  Value
L3  00
Back