13
  < B.  Hanging Indoor Unit 
  without Suspension Bracket >
 (Ifthereisnotenoughservicespace
betweentheceilingandtheindoorunit,hang
theindoorunitbymethodA.)
(a) Determinethepositiontoinstallthe
suspensionbolt.
(b) Fixthewasherandnuttothesuspension
bolt.
(c) Mounttheindoorunittothesuspension
bolts.
  NOTE: 
Theceilingsurfacemaynotbehorizontal.
Whentheindoorunitismounted,check
thelevelnessbyaleveltobethedrainpipe
connectiondown-slope.Iftheindoorunitis
mountedwithincorrectsuspendingposition,
itmaydeformandtheabnormalvibration
mayoccur.
(3) Whentheindoorunitismounted,create
down-slopetowarddrainpipeconnection
tobewelldrainage.Therightgureshows
therightdrainpipeconnection.(Before
shipment)Fortheleftdrainpipeconnection,
createdown-slopetowardleft.
4.3.4 InstallationofWiredController
Theinstallationofwiredcontrollershallbe
performedaccordingtotheinstallationmanualof
itself.
(4) Attachthesidecoverandthesupporting
string.
(5) Removetheprotectionlmattachedtothe
louversurface.
(6) Removetheprotectiontapeattachedtothe
airinletlter.
Ceiling
Suspension Bolt (Field-Supplied)
Nut (Field-Supplied)
Washer (Field-Supplied)
Max. 50mm
Nut (Field-Supplied)
Washer (Field-Supplied)
View from Front
(Drain Pipe Connection)
1 ~ 10mm
1 ~ 10mm
Lower the indoor unit
10mm when the optional
drain-up mechanism is
installed.