A10762300A-rev.1 
21
7.  Electrical Wiring
● Wrap the accessory packing around the 
wires, and plug the wiring connection hole 
with the seal material to protect the product 
from any condensate water or insects.
● Tightly secure the wires with the cord clamp 
inside the indoor unit.
● Lead the wires through the knockout hole in 
the side cover when using conduit.
● Secure the cable of the wired controller using 
the cord clamp inside the electrical box.
7.1 GeneralCheck
(1) Makesurethattheeld-selectedelectrical
components(mainpowerswitches,circuit
breakers,wires,conduitconnectorsand
wireterminals)havebeenproperlyselected
accordingtotheelectricaldatagivenin
“TechnicalCatalog”.Makesurethatthe
componentscomplywithNationalElectrical
Code(NEC).
(2) Usetheshieldedtwistpaircableforthe
controlcablebetweentheoutdoorunitand
theindoorunit,thecontrolcablebetween
indoorunitsandthecontrollercableof 
PC-ARF1.
(3) Checktoensurethatthepowersupply
voltageiswithin±10%oftheratedvoltage.
(4) Checkthecapacityoftheelectricalwires. 
Ifthepowersourcecapacityistoolow,the
systemcannotbestartedduetothevoltage
drop.
(5) Checktoensurethattheearthwireis
connected.
Theprocedureofthewiringworkshallbe
performedaccordingtothismanualand“Installation
&MaintenanceManual”oftheoutdoorunit.
● The electrical wiring work must be performed 
by authorized installers.  If not, it may cause 
an electric shock or a re.
● Perform the electrical work according to 
each regulation of region and “Installation 
& Maintenance Manual”, and the dedicated 
electrical circuit must be used.  If not 
performing the electrical wiring work 
completely or a capacity shortage of the 
power circuit, it will cause an electric shock 
or a re.
● Use the specied cables for wiring between 
the outdoor unit and indoor units.  Selecting 
incorrect cables will cause an electric shock 
or a re.
● Install an ELB (Earth Leakage Breaker) in the 
power source.  If not used, it will cause an 
electric shock or a re.
● Turn OFF the main power switch of the 
indoor unit and the outdoor unit before an 
electrical wiring work or a periodical check 
is performed.  If not, it will cause an electric 
shock or a re.
● Check to ensure that the indoor fan and the 
outdoor fan have stopped before electrical 
wiring work or a periodical check is 
performed.
● Protect the wires, drain pipe, electrical parts, 
etc. from rats or other small animals. 
If not protected, rats may gnaw at unprotected 
parts and at the worst, a re will occur.
● Tighten screws according to the following 
torque.
  M3.5: 1.2 N-m 
  M4:  1.0 to 1.3 N-m
● Connect earth wires for the outdoor / indoor 
unit to prevent an electrical shock or an 
unexpected accident.  The earth resistance 
must be less than 1 megohm.   The earth work 
must be performed by authorized installers.
● Turn completely OFF the power source to 
prevent an electrical shock when opening the 
service cover to perform the electrical work 
or the maintenance.
● Pay attention not to bite electrical wirings 
when attaching the service cover. It may 
cause an electrical shock or re.