40 
A10762300A-rev.1
8.1 BeforeTestRun
Recheckthatthereisnotanyproblemstothe
installation,anddonotperformthetestrununtilall
thefollowingcheckingpointshavebeencleared.
(1) Checktoensurethattherefrigerantpiping
andthetransitionwiringareconnectedtothe
samerefrigerantcyclesystem.Ifnot,itwill
causeanabnormaloperationandbreakage
ofinstruments.
(2) Checktoensurethattheelectricalresistance
ismorethan1megohm,bymeasuringthe
resistancebetweengroundandtheterminal
oftheelectricalparts.Ifnot,doNOToperate
thesystemuntiltheelectricalleakageis
foundandrepaired.Donotapplythehigh
voltagetotheterminalsforthetransmission
(TB2(A,B,1and2)).
8.  Test Run
Testrunshouldbeperformedaccordingtothis
manualand“Installation&MaintenanceManual”of
theoutdoorunit.
Donotoperatethesystemuntilallthecheckpoints
havebeencleared.
●  Check to ensure that the electrical resistance 
is more than 1 megohm, by measuring the 
resistance between ground and the terminal 
of the electrical parts.  If not, do not operate 
the system until the electrical leakage is 
found and repaired.
●  Do not touch any of the parts at the discharge 
gas side by hand while the system is running, 
since the compressor chamber and the pipes 
at the discharge side are heated higher than 
90
o
C.
● Checktoensurethatthestopvalvesofthe
outdoorunitarefullyopened,andthenstartthe
system.
● Checktoensurethattheswitchonthemain
powersourcehasbeenONformorethan
12hours,towarmthecompressoroilbythe
crankcaseheater.
(3) Checktoensurethateachwireiscorrectly
connectedatthepowersource.Ifincorrectly
connected,theunitwillnotoperateand
thewiredcontrollerwillindicatethealarm
code“05”.Inthiscase,checkthephase
oftheprimarypowersourceaccordingto
theattachedattentionlabelontherearside
oftheservicecover.Then,performthe
reconnectionworkcorrectlywithturningOFF
thepowersupply.
(4) Checktoensurethatthemainpowersource
hasbeenturnedONformorethan12hours,
towarmthecompressoroilbythecrankcase
heater.
8.2 TestRun
Aftertheinstallationworkiscompleted,testrun
shouldbeperformed.
(1) Checktoensurethatstopvalves(gasand
liquid)oftheoutdoorunitarefullyopened.
(2) Inthecasethatindoorunitsareconnected
totheVRFsystem,performthetestrunof
theindoorunitonebyonesequentiallyand
thencheckaccordanceoftherefrigerant
pipingsystemandtheelectricalwiring
system.(Ifthemultipleindoorunitsare
operatedsimultaneously,thesystemcannot
beinspectedthesystemaccordance.)
(3) Performthetestrunaccordingtothe
followingprocedure.Ensurethatthetestrun
iscarriedoutwithoutanyproblem.
(a) Pressandhold“Menu”and“Back/Help”
simultaneouslyforatleast3seconds. 
Thetestrunmenuwillbedisplayed.
1)Thetestrunmenuwillbedisplayed.
TestRunScreen
NOTE
When“00unit”isindicated,theauto-
addressfunctionmaybeperforming. 
Cancel“TestRun”modeandsetitagain.
Back
Adj.Sel. ON Rtrn
Test Run Setting: 2 units
MODE
SPEED
AUTO
COOL