1-107
TROUBLESHOOTING
1.3.3 Self-Checking of Indoor Unit PCB
(Except for:  RCI, RCD, RPI (0.8 to 5.0HP), RPC (After Alteration) and KPI)
(1) Self-Checking by Relays on Indoor Unit PCB
  • To Check Abnormality on Indoor Unit PCB due to Malfunction
  • To check Abnormality on Indoor Unit PCB Based on Results of Checking by CHECK switch on the
remote control switch and Self-Checking Function
■ Procedure
Refer to pages 1-94, 95 for location and function of DSW and LED.
a) Turn OFF the main power switch.
b) Disconnect connectors CN5 and CN8, and set dip switch DSW2 as shown below.
NOTE: Before turning ON the power, see checking procedure mentioned in next page.
c) Turn ON the main power switch.
Check Mode starts. (See next page.)
* Analog Test
* Relay Test
d) After completion of self-checking, turn OFF the power and reset the dip switch as before.
1
Dip Switch DSW2
Set #1 at ON side and #2 at OFF side.
ON
OFF
2 3 4 5 6 7 8