4 Electrical wiring
134
SMGB0077 rev.0 - 01/2013
Part
1 Terminal box (TB1)
2 Terminal box (TB2)
3 Outlet air thermistor
4 Connector for the swing louver motor
5 Printed circuit board (PCB)
6 Earthing screw
7 Remote control wiring
8 Communication wiring
9 Power wiring
10 Tie
Part
1 Cord clamp
2 Remote control switch cable
3
Transmission wiring (outdoor unit to indoor unit and
viceversa)
3
Test runs
C A U T I O N
Be careful during the test runs, as some of the safety functions remain disabled: the units operate for two
hours without switching off via the thermostat. The three-minute compressor protection is not enabled during
the test.
Secure the rubber bushes to the panel using adhesive when the outdoor unit ducts are not used.
The compressor remains at a standstill during forced stoppage.
4.1.4 Electrical connection of RCD units
Work prior to the electrical connection
1 Turn off the power supply switches before starting work and t the appropriate locks and safety warnings.
2 Wait 5 minutes after turning off the power supply switches.
3 Check that the fans on the indoor and outdoor units are at a standstill before starting work.
N O T E
Theelectricalpowerfortheunitmustinvolveaspecicpowerline,withanexclusivepowercontrolswitchand
residual current breaker, installed in line with local or national safety regulations.
Check that the electrical power line has enough capacity to supply the unit. Its length, the cable diameter and
their protection (sleeve or jacket) must be appropriate for the unit.
For further information, always consider the current regulations in the country where the unit is to be installed.