4 Electrical wiring
150
SMGB0077 rev.0 - 01/2013
Test runs
C A U T I O N
Be careful during the test runs, as some of the safety functions remain disabled: the units operate for two
hours without switching off via the thermostat. The three-minute compressor protection is not enabled during
the test.
Secure the rubber bushes to the panel using adhesive when the outdoor unit ducts are not used.
The compressor remains at a standstill during forced stoppage.
4.1.10 Electrical connection of KPI units
Work prior to the electrical connection
1 Turn off the power supply switches before starting work and t the appropriate locks and safety warnings.
2 Wait 5 minutes after turning off the power supply switches.
3 Check that the fans on the indoor and outdoor units are at a standstill before starting work.
N O T E
Theelectricalpowerfortheunitmustinvolveaspecicpowerline,withanexclusivepowercontrolswitchand
residual current breaker, installed in line with local or national safety regulations.
Check that the electrical power line has enough capacity to supply the unit. Its length, the cable diameter and
their protection (sleeve or jacket) must be appropriate for the unit.
For further information, always consider the current regulations in the country where the unit is to be installed.
C A U T I O N
Riskofre:cablesmustnevertouchtherefrigerantpipes,printedcircuitboards(PCB),sharpedgesorelec-
trical components inside the unit to avoid damaging them.
Loose connection terminals may lead to cable and terminal overheating. The unit may operate incorrectly,
leadingtoariskofre.Checkthatthecablesarermlysecuredtotheconnectionterminals.
Electrical connection
Cut the centre of the rubber bushing in the wiring connection
knockout hole.
Follow the steps below to connect the remote control cable or the
optional extension wire:
1 Pass the cable through the knockout hole in the cabinet.
2 Connect the cable to the terminals on the printed circuit board
(PCB) located inside the electrical box.
3 Tighten the screw on terminals A and B in the electrical box.
4 Check that the cables are correctly secured.
Part
1 Remote Control
2 Transmission Wires
3 Power supply wires (Single phase)
4 Earth Screw
1
4
3
2