3. REFRIGERANT PIPING
3.1. PIPING CONNECTION
NOTE: RPK-(1.0-1.5)FSNH2M (models to mount the
expansion valve outside units).
1. Installation of optional expansion valve kit is
required when installing refrigerant piping. See also
the ‘Installation and Operation Manual' of the
expansion valve kit for then installation work,
connecting pipe size, additional refrigerant charge
volume and the number of connectable units.
2. The temperature of the liquid pipe between the
expansion valve kit and indoor unit decreases
lower the standard models; additional insulation
work may be required depending on the
environment.
3.1.1. PIPING POSITION
Position of piping connection is the following, which is
available from all directions, top, left or right.
RPK-(1.0-1.5)FSNH2M, (models to mount the expansion
valve outside units) may generate refrigerant circulation
noise; take out the pipe from the right rear side whenever
possible, instead of the left rear side.
Q Gas Piping Position
Model RPK-(0.8-4.0)FSN2M
(mm)
HP
Model RPK-(1.0-1.5)FSNH2M
(mm)
HP
Q Liquid Piping Position
Model RPK-(0.8-4.0)FSN2M
(mm)
HP
Model RPK-(1.0-1.5)FSNH2M
(mm)
HP
CAUTION:
- Do not twist the pipe and hold the base well when
bending the tube.
- Only for RPK-2.0 HP
In the case that gas piping diameter is Ø12.7, remove the
union attached to the unit.
Q Right, Left and Rear Side Position
1. Right Side Piping
Cut the corner using a plastic cutter as shown
below and remove sharp edges completely.
2. Left Piping
Cut the corner at the left side using a plastic cutter
same as the right side piping (*1).
(*1) RPK-(1.0-1.5)FSNH2M, (models to mount the
expansion valve outside units) may generate refrigerant
circulation noise; take out the pipe from the right rear side
whenever possible, instead of the left rear side.
Refrigerant pipe
(liquid)