DSW7: Fuse Recover and Remote control
switch system
- (0.8-1.5) HP
Not setting is required. Setting position
before shipment is OFF.
In case of applying high voltage to the
terminal 1,2 of TB1, the fuse on the
PCB1(M) is cut.
In such a case, firstly correct the wiring to
TB1 and then turn on (as showing
beside)
- (2.0-4.0) HP
Not setting is required. Setting position
before shipment is all OFF.
In case of applying high voltage to the
terminal 1,2 of TB1, the fuse on the
PCB1(M) is cut.
In such a case, firstly correct the wiring to
TB1 and then turn on #1. (as showing
beside)
Do not turn the air louver by hand. If moved, the
louver mechanism will be damaged! (in all units)
Adjust the vertical deflectors by hand to discharge air in the
required direction.
Do not swing 1 blade at left
side and 2 blade at right side of the
vertical deflection.
Automatic Setting of louver:
When the unit operation is stopped, two air louvers are stopped at
closing position automatically.