S1 series standard inverter
-99-
Detailed parameter description
to prevent overcurrent fault caused by DC brake
during high speed.
DC brake current after stop: it means the DC
brake force applied, the larger the current, the
stronger the DC brake effect.
P01.04
Acceleration
P13.14
P01.23
Constant speed
In running
Deceleration
P01.10
P13.15
P01.12
P01.09
Time t
Setting range of P01.09: 0.00Hz–P00.03 (Max.
output frequency)
Setting range of P01.10: 0.00–30.00s
Setting range of P01.11: 0.0–100.0%
Setting range of P01.12: 0.0–50.0s
Deadzone time of
forward/reverse
rotation
This function code refers to the transition time of
the threshold set by P01.14 during setting
forward/reverse rotation of the inverter, as shown
below.
Output frequency f
Forward
Reverse
Deadzone
time
Time t
Starting
frequency
Switch over after
zero frequency
Switch over after
starting frequency
Setting range: 0.0–3600.0s
Forward/reverse
rotation
switch-over mode
0: Switch over after zero frequency
1: Switch over after starting frequency
2: Switch over after passing stop speed and delay
Stop speed
detection mode
0: Set value of speed (the only detection mode
valid in V/F mode)
1: Detection value of speed
Stop speed
detection time
When the running command channel is controlled
by terminals, the system will detect running