S1 series standard inverter
-119-
Function
code
Name
Detailed parameter description
Default
value
Modify
FWD
REV
COM
Sln
SB2
SB1
SB3
Sln
FWD
REV
Running
direction
ON
OFF→ON
ON
Forward
OFF
Forward
ON
ON
OFF→ON
Reverse
OFF
Reverse
ON→OFF
Decelerate
to stop
Sln: 3-wire control/Sin, FWD: Forward running,
REV: Reverse running
Note: For dual-line running mode, when
FWD/REV terminal is valid, if the inverter stops
due to stop command given by other sources, it
will not run again after the stop command
disappears even if the control terminals
FWD/REV are still valid. To make the inverter run
again, users need to trigger FWD/REV again.
P05.12
S1 terminal
switch-on delay
These function codes define corresponding delay
of the programmable input terminals during level
variation from switch-on to switch-off .
Si electrical level
Si valid
invalid invalid
Switcn-on
delay
Switcn-off
delay
valid
Setting range: 0.00050.000s
Note: After a virtual terminal is enabled, the state
of the terminal can be changed only in
communication mode. The communication
0.000s
P05.13
S1 terminal
switch-off delay
0.000s
P05.14
S2 terminal
switch-on delay
0.000s
P05.15
S2 terminal
switch-off delay
0.000s
P05.16
S3 terminal
switch-on delay
0.000s
P05.17
S3 terminal
switch-off delay
0.000s