S1 series standard inverter
-133-
Function
code
Name
Detailed parameter description
Default
value
Modify
P08.35
FDT2 lag
detection value
level-FDT lag detection value), the waveform is
shown in the figure below.
Time t
Output frequency f
FDT level
FDT lag
Y1,
RO1, RO2
Time t
Setting range of P08.32: 0.00HzP00.03 (Max.
output frequency)
Setting range of P08.33: 0.0100.0% (FDT1 level)
Setting range of P08.34: 0.00HzP00.03 (Max.
output frequency)
Setting range of P08.35: 0.0100.0% (FDT2 level)
5.0%
P08.36
Detection value
for frequency
arrival
When the output frequency is within the positive
/negative detection range of the set frequency, the
multi-function digital output terminal outputs
"frequency arrival" signal as shown below.
Y,
RO1, RO2
Output frequency
Set
frequency
Detection amplitude
Time t
Time t
Setting range: 0.00HzP00.03 (Max. output
frequency)
0.00Hz
P08.37
Enable/disable
energy-
consumption
brake
0: Disable energy-consumption
1: Enable energy-consumption
1
P08.38
Energy-
consumption
brake threshold
Set the starting bus voltage of
energy-consumption brake, adjust this value
properly can brake the load effectively. The
230V
voltage:
380.0V;