Detailed parameter description
level-FDT lag detection value), the waveform is
shown in the figure below.
Time t
Output frequency f
FDT level
FDT lag
Y1,
RO1, RO2
Time t
Setting range of P08.32: 0.00Hz–P00.03 (Max.
output frequency)
Setting range of P08.33: 0.0–100.0% (FDT1 level)
Setting range of P08.34: 0.00Hz–P00.03 (Max.
output frequency)
Setting range of P08.35: 0.0–100.0% (FDT2 level)
Detection value
for frequency
arrival
When the output frequency is within the positive
/negative detection range of the set frequency, the
multi-function digital output terminal outputs
"frequency arrival" signal as shown below.
Y,
RO1, RO2
Output frequency
Set
frequency
Detection amplitude
Time t
Time t
Setting range: 0.00Hz–P00.03 (Max. output
frequency)
Enable/disable
energy-
consumption
brake
0: Disable energy-consumption
1: Enable energy-consumption
Energy-
consumption
brake threshold
Set the starting bus voltage of
energy-consumption brake, adjust this value
properly can brake the load effectively. The