S1 series standard inverter
-135-
Function
code
Name
Detailed parameter description
Default
value
Modify
terminal control
setup
Ones: Frequency control selection
0: UP/DOWN terminal setup is valid
1: UP/DOWN terminal setup is invalid
Tens: Frequency control selection
0: Valid only when P00.06=0 or P00.07=0
1: All frequency modes are valid
2: Invalid for multi-step speed when multi-step
speed takes priority
Hundreds: Action selection during stop
0: Valid
1: Valid during running, clear after stop
2: Valid during running, clear after receiving stop
command
P08.45
UP terminal
frequency
incremental
integral rate
0.0150.00Hz/s
0.50Hz/s
P08.46
DOWN terminal
frequency
decremental
change rate
0.0150.00Hz/s
0.50Hz/s
P08.47
Action selection
for frequency
setup during
power down
0x0000x111
Ones: Action selection for frequency setup (by
keypad digits) during power down
0: Save during power down
1: Zero out during power down
Tens: Action selection for frequency setup (by
Modbus) during power down
0: Save during power down
1: Zero out during power down
Hundreds: Action selection for frequency setup
(by other communication) during power down
0: Save during power down
1: Zero out during power down
0x000
P08.48
High bit of initial
value of power
consumption
Set the initial value of power consumption.
Initial value of power
consumption=P08.48×1000+ P08.49
Setting range of P08.48: 059999 kWh (k)
Setting range of P08.49: 0.0999.9 kWh
P08.49
Low bit of initial
value of power
0.0°