S1 series standard inverter
-86-
Detailed parameter description
0: AI1
1: AI2
2: AI3
3: High-speed pulse HDIA
4: Modbus communication
5 - 10: Reserved
PID output characteristics
0: PID output is positive characteristic
1: PID output is negative characteristic
Limit of PID control
deviation
Upper limit value of PID
output
P09.10–100.0% (max. frequency or
voltage)
Lower limit value of PID
output
-100.0%–P09.09 (max. frequency or
voltage)
Feedback offline detection
value
Feedback offline detection
time
0x0000–0x1111
Ones:
0: Continue integral control after the
frequency reaches upper/lower limit
1: Stop integral control after the
frequency reaches upper/lower limit
Tens:
0: The same with the main reference
direction
1: Contrary to the main reference
direction
Hundreds:
0: Limit as per the max. frequency
1: Limit as per A frequency
Thousands: