4-10
Chapter 4
For parameter configuration
[AA111] to [AA115][bb-40]
RUN command selection
Code/Name
Range (unit)
Initial value
AA111
RUN command
input source
selection,
1st-motor
00([FW]/[RV] terminal)
01(3-wire)
02(Keypad’s RUN-key)
03(RS485)
04(Option-1)
05(Option-2)
06(Option-3)
02(JPN)/
00(EU)
(USA)
(ASIA)
(CHN)
Select in which way will be operated.
In case it does not work, please review it.
Keypad keys settings
Code/Name
Range (unit)
Initial value
AA-12 RUN-key
command rotation
direction
00(Forward)/
01(Reverse)
00
AA-13
STOP key enable
00(Disable)/01(Enable)/
02(Enable at only at trip reset)
01
[AA-12] specifies in which direction (forward/reverse) will be
the rotation after pressing the RUN key in the operation
keypad.
[AA-13] changes the behavior of the STOP key of keypad. When
01 (enable) (initial value) is set, the STOP key performs stop
operation regardless of the run command selection. When
stopping only with the command selected in the run
command selection, change it to 00(disabled). If the run
command selection [AA111] is set to 02(Keypad’s RUN key),
the STOP key on the Keypad is valid regardless of the [AA-13]
setting.
RUN command direction restriction
Code/Name
Range (unit)
Initial value
AA114 RUN direction
restriction,1st-motor
00(No restriction)/
01(Only forward)/
02(Only reverse)
00
In the case of an incorrect RUN command, [AA114] setting
prevents the output from unintended rotation.
Restart operation after decel/free-run STOP
Code/Name
Range (unit)
Initial value
AA115 STOP mode
selection, 1st-motor
00(Deceleration stop)/
01(Free-run stop)
00
bb-40
Restart mode after FRS
release
00(Restart at 0Hz)/
01(Restart with matching
frequency)/
02(Restart with active
frequency matching)/
03(Detect speed) *1)
00
*1) This function requires encoder feedback to the P1-FB option or to
the input terminals [A]/[B] assigned the function 103[PLA]/104[PLB].
In the [AA115], deceleration stop or free-run stop can be
selected when a stop command is executed.
If input terminal 032[FRS] is active (ON), free-run stop is
possible.
In the [bb-40], the restart method after the release of the
032[FRS] and the restart method after the free-run at the stop
are selected.
If the overvoltage error [E007] occurs during deceleration, if
the motor is allowed to stop coasting, the [E007] will be
avoided by free-run stop by setting the [AA115] to 01
(Free-run stop).
[AA121] to [AA223]
Control mode selection
Code/Name
Range (unit)
Initial
value
AA121
Control mode
selection,
1st-motor
00 ([V/f] Fixed torque characteristics (IM))/
01 ([V/f] Reducing torque characteristics (IM))/
02 ([V/f] Free V/f (IM))/
03 ([V/f] Auto torque boost (IM))/
04 ([V/f with encoder]
Fixed torque characteristics (IM)/
05 ([V/f with encoder]
Reduced torque characteristics (IM)/
06 ([V/f with encoder] Free V/f (IM)/
07 ([V/f with encoder] Auto torque boost (IM)/
08 (Sensorless vector control (SLV) (IM))/
09 (0Hz-range sensorless vector control(0Hz-SLV)
(IM)) /
10 (Vector control with encoder (CLV)(IM)) /
11(Synchronous start type
sensorless vector control(SM/PMM))/
12 (IVMS start type sensorless vector control
(SM/PMM))
00
Generally for a light duty control (such as fans or pumps), the
[V/f] control with constant torque or the [V/f] control with
reducing torque characteristics similar to the operation
characteristics of fans and pumps is selected.
For heavy duty (Cranes, etc…), sensorless vector control
(SLV)is the typically used. If heavy torque is required at
startup, closed loop vector control(CLV) or 0Hz-range
sensorless vector control(0Hz-SLV) will be used.
For a magnet motor select the sensorless vector control
(SM/PMM).
With the Load Type(Ub-03) is in standard duty (ND) all the setting
items are available. But the Load type is in Low duty (LD), 09 and 10 is
not available. And at the Load type in very low duty (VLD), 09, 10 and
12 is not available.
SH1-03410-H(SH1-1600H)~SH1-04810-H(SH1-2200H)support only
normal duty(ND)and low duty(LD).
Vector control with encoder mode
Code/Name
Range (unit)
Initial value
AA123
Vector control
mode selection,
1st-motor
00(Speed/Torque control mode)/
01(Pulse train position control)/
02(Position control)/
03(High-resolution position control)
00
Torque control is effective only when the AA121 setting is 08 to
12 and the AA123 settting is 00.
Pulse train position control is effective only when the AA121
setting is 10 and the AA123 setting is 01, And input trminal
073[STAT] is assignd and must be ON.
Absolute position control is effective only when the AA121
setting is 10 and the AA123 setting is 02 or 03.
For more information, contact to your supplier or local Hitachi
sales office.
2nd motor When Intelligent Input terminal 024[SET] is enabled.
Code/Name
Range
(unit)
Initial
value
AA201 Main speed input source selection,
2nd-motor
Same as AA101
AA202 Sub speed input source selection,
2nd-motor
Same as AA102
AA204 Sub speed setting, 2nd-motor
Same as AA104
AA205 Speed reference calculation symbol
selection, 2nd-motor
Same as AA105
AA206 Add frequency setting, 2nd-motor
Same as AA106
AA211 RUN-command input source
selection, 2nd-motor
Same as AA111
AA214 RUN-direction restriction selection,
1st-motor
Same as AA114
AA215 STOP mode selection, 2nd-motor
Same as AA115
AA221 Control mode selection 2nd-motor
Same as AA121
AA223 Vector control mode selection,
2nd-motor
Same as AA123